Event List (683188)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Office DeltaV 2021-09-27 14:02:00 357 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:59 338 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 345 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 355 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 361 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 365 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 4225 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]IO: No Communications On Port - Serial Card, C05, P01
SHP Office DeltaV 2021-09-27 14:01:59 4393 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:59 5825 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:59 9353 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 9376 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:59 9378 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:58 9333 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:58 9345 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:58 9351 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:58 9366 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:58 9373 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:58 9394 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:58 9408 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:54 8630 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 14:01:40 2770 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 14:01:40 4346 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:40 4362 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:40 5816 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:39 1795 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 14:01:39 3216 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2021-09-27 14:01:39 3938 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 14:01:39 4341 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:39 4352 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:39 4357 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:39 4368 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:39 4374 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:39 4395 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:39 5812 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 14:01:39 9339 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:29 4346 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/PARAM2 Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:29 4348 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/PARAM1 Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 14:01:28 240 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 14:01:28 940 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 14:01:28 4284 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 14:01:28 7687 DOWNLOAD USER BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-09-27 14:01:28 7779 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 14:00:44 7060 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 14:00:29 4191 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-09-27 14:00:29 5580 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 14:00:27 482 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 14:00:27 3987 DOWNLOAD USER BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-09-27 14:00:27 4087 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:59:10 285 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:10 4289 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:10 5899 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:10 9380 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:59:09 332 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:09 333 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:09 334 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:09 4156 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]IO: No Communications On Port - Serial Card, C05, P01
SHP Office DeltaV 2021-09-27 13:59:09 4291 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:09 9492 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:09 9493 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:08 258 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:08 266 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:08 273 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:08 282 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:08 286 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:08 4293 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:08 5744 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:59:07 9249 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:07 9261 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:07 9266 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:07 9278 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:07 9284 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:07 9302 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:59:07 9316 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:58:56 1500 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:58:56 4268 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:56 4284 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:58:56 5736 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:58:55 1423 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:58:55 2879 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2021-09-27 13:58:55 3573 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:58:55 4140 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-09-27 13:58:55 4255 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 4267 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 4274 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 4286 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 4293 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 4313 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:58:55 5735 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:58:55 9257 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 9259 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 9271 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 9274 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:55 9278 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_03_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:58:54 6830 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:58:54 7770 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:52:18 73 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:52:18 4100 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:52:18 5550 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:48 60 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:48 62 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:48 63 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:47 42 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 47 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 53 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 59 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 62 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 9062 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 9085 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:47 9087 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:46 4044 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:46 4054 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:46 4057 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:46 4067 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:46 4070 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:46 4089 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:46 5533 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:46 9069 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:46 9082 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:02 37 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:02 4058 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:02 5515 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:01 40 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:01 42 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:01 43 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:00 24 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 29 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 35 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 39 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 44 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 4057 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:00 5514 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:51:00 9041 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 9063 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:51:00 9064 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:59 9022 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:59 9031 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:59 9037 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:59 9047 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:59 9050 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:59 9066 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:59 9080 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:48 32 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:48 4054 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:48 5507 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:18 20 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:18 22 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:18 23 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:18 4037 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:18 5491 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:17 2 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 7 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 17 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 20 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 24 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 4025 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 4041 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:17 5491 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:17 9036 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:17 9038 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:16 4002 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:16 4012 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:16 4015 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:16 4026 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:16 4030 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:16 4049 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:16 5490 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:50:16 9029 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:50:16 9042 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:28 4015 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:28 5471 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:27 2 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:27 3 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:27 4 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:27 3873 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]IO: No Communications On Port - Serial Card, C05, P01
SHP Office DeltaV 2021-09-27 13:49:27 9994 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:26 0 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:26 4 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:26 4012 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:26 5469 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:26 8995 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:26 9019 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:26 9020 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:25 8975 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 8986 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 8991 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 9005 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 9010 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 9030 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 9044 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:49:25 9980 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 9987 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:25 9994 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:49:04 2100 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:48:49 4060 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:48:45 505 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2021-09-27 13:48:45 1157 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:48:44 5210 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:48:44 5910 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:48:44 9331 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:48:29 8090 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:48:14 8800 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:48:13 3840 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-09-27 13:48:13 8989 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 3965 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 3968 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 3977 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 3981 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 3984 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_03_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 8964 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 8986 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 8988 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:12 8989 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:48:11 1820 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:48:11 2760 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:48:11 6413 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:48:11 7879 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2021-09-27 13:48:11 8513 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:48:11 8946 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:11 8957 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:11 8963 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:11 8974 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:11 8979 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:11 8998 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:48:11 9011 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:28 3820 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:28 5275 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:27 9799 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:26 8801 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:26 8824 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:26 8825 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:26 9802 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:26 9804 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:25 3821 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:25 5274 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:25 9797 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:24 8781 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 8789 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 8793 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 8805 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 8808 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 8825 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 8838 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:42:24 9786 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 9791 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 9801 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 9804 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:42:24 9807 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:33:15 3567 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:33:15 5019 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:33:14 9542 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:32:52 8543 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:52 8565 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:52 8566 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:32:52 9546 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:52 9548 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:38 3550 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:32:38 5007 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:32:38 9531 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:32:37 8512 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 8521 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 8524 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 8534 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 8538 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 8554 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 8569 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:32:37 9518 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 9523 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 9529 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 9532 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:32:37 9535 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:57 3499 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:57 4949 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:56 9471 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:55 8470 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:55 8493 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:55 8494 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:55 9474 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:55 9475 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:55 9477 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:54 3456 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 3466 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 3469 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 3479 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 3482 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 3501 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:54 4942 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:54 8477 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 8489 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:30:54 9451 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 9456 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 9462 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 9465 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:30:54 9468 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:28 3435 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:28 4890 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:27 3438 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:27 4889 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:27 9419 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:26 9411 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:26 9413 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:26 9414 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:25 9393 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:25 9399 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:25 9404 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:25 9407 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:25 9410 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:07 3428 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:07 4880 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:06 3425 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:06 4881 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:06 9403 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:05 3417 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:05 3432 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:05 4879 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:05 8425 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:05 8427 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:05 9407 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:05 9408 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:05 9409 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:04 3395 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 3405 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 3411 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 3423 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 3429 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 3450 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:04 4879 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:04 8414 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 8427 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:29:04 9388 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 9395 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 9402 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 9408 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:29:04 9412 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:27 3189 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]IO: No Communications On Port - Serial Card, C05, P01
SHP Office DeltaV 2021-09-27 13:25:27 6140 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:25:13 8326 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 3301 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 3304 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 3314 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 3317 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 3322 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_03_O Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 6540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:25:12 8303 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 8326 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 8327 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:12 8328 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:25:11 1870 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:25:11 2810 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:25:11 6471 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:25:11 6615 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2021-09-27 13:25:11 7115 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:25:11 8282 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:11 8293 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:11 8298 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:11 8308 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_01 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:11 8314 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI0/REGISTER_02 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:11 8333 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:25:11 8346 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:23:00 9600 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:22:47 3267 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:47 4717 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:46 2340 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:22:46 9240 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:45 3265 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:45 4716 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:45 8264 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:45 9252 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:44 3252 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:44 8252 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:44 8275 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:44 8276 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:44 9249 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:44 9250 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:43 1920 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:22:43 2850 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:22:43 6490 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:22:43 7837 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2021-09-27 13:22:43 8223 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8235 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8239 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8248 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_0_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8252 EVENT PROCESS BOILER CNTRL01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/BC01_AI1/REGISTER_1_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8266 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_IN Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8282 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/REGISTER_OUT Outputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 8284 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:22:43 8600 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:22:43 9229 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 9235 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 9243 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 9248 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:22:43 9252 EVENT PROCESS BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Office DeltaV 2021-09-27 13:19:42 5970 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:19:26 7160 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:19:14 6125 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 21.3278 Limit 80
SHP Office DeltaV 2021-09-27 13:19:14 6127 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature HI_ALM INACT/ACK 11-WARNING HIGH High Alarm Value 21.3278 Limit 60
SHP Office DeltaV 2021-09-27 13:19:14 6129 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 21.3278 Limit 400
SHP Office DeltaV 2021-09-27 13:19:14 6130 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 21.3278 Limit 250
SHP Office DeltaV 2021-09-27 13:19:14 6132 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 21.3278 Target 20
SHP Office DeltaV 2021-09-27 13:19:14 6134 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 21.3278 Target 20
SHP Office DeltaV 2021-09-27 13:19:14 6135 ALARM INSTRUMENT BOILER CNTRL01 PIC101 TIC102 Boiler temperature PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:19:13 2997 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:19:13 3310 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold start memory download is preempted
SHP Office DeltaV 2021-09-27 13:19:13 6241 DOWNLOAD USER BOILER CNTRL01 PIC101 TIC102 Boiler temperature UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-09-27 13:19:13 6313 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:19:10 8160 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:19:09 5607 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2021-09-27 13:19:09 5608 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2021-09-27 13:19:09 5609 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:19:08 5612 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 I/O Input Failure
SHP Office DeltaV 2021-09-27 13:19:08 5613 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 Module Failure Active
SHP Office DeltaV 2021-09-27 13:19:08 5615 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 8
SHP Office DeltaV 2021-09-27 13:19:08 5617 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 4
SHP Office DeltaV 2021-09-27 13:19:08 5619 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2021-09-27 13:19:08 5620 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2021-09-27 13:19:08 5622 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2021-09-27 13:19:08 5623 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2021-09-27 13:19:08 5624 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 13:19:07 4388 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:19:07 8442 DOWNLOAD USER BOILER CNTRL01 PIC101 Steam Pressure UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-09-27 13:19:07 8547 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:09:28 1919 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2021-09-27 13:09:27 7630 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2021-09-27 13:09:26 6400 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-09-27 13:09:26 9919 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2021-09-27 13:09:24 7919 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-09-27 13:09:24 7924 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-09-27 13:09:19 9160 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-09-27 13:08:44 4110 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-09-27 13:08:44 4110 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-09-27 13:08:32 8040 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 13:08:29 2709 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/ACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-09-27 13:08:29 3880 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2021-09-27 13:08:29 3880 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2021-09-27 13:08:27 6670 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 13:08:19 8250 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-09-27 13:08:18 8110 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 13:08:13 6740 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 13:08:06 7888 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:08:04 1110 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-09-27 13:07:35 4367 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:07:10 4853 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:06:45 4844 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:06:24 4747 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-09-27 13:06:20 5335 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:05:55 6322 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:05:52 4731 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-09-27 13:05:42 780 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-09-27 13:05:30 6311 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:05:15 6310 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-09-27 13:05:05 8299 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:04:50 2785 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 13:04:48 7784 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-09-27 13:04:43 9050 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-09-27 13:04:21 7060 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-09-27 13:04:05 4200 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-09-27 13:04:05 9190 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-09-27 13:03:35 1388 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-09-27 13:03:35 1426 CHANGE USER AREA_A PROPLUS CNTRL01 ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-09-27 13:03:35 2563 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/ACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 13:03:11 4654 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-09-27 13:02:55 4646 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-09-27 13:01:57 4618 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-09-27 13:01:49 9020 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-09-27 13:01:48 4610 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-09-27 13:01:37 5293 CHANGE USER BOILER PROPLUS LS107 Boiler HIHI Level ENABLED.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-09-27 13:01:29 7780 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:01:28 6240 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold start memory download is preempted
SHP Office DeltaV 2021-09-27 13:01:28 7270 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 13:01:28 9890 DOWNLOAD USER BOILER CNTRL01 LS107 Boiler HIHI Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-09-27 13:01:28 9954 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:01:24 5410 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-09-27 13:01:21 445 DOWNLOAD USER BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-09-27 13:01:21 543 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-09-27 13:01:20 7776 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-09-27 12:59:16 2040 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-09-27 12:58:59 2441 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 12:58:42 8018 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-09-27 12:58:34 8014 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-09-27 12:57:33 2589 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-09-27 12:57:29 2405 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/ACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-09-27 12:57:15 2395 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/ACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-09-27 12:57:14 5779 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-09-27 12:57:12 8506 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-09-27 12:57:11 4660 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2021-09-27 12:57:11 8519 CHANGE USER BOILER PROPLUS BUS_COUPLER_01 Phoenix Contact Remote IO ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-09-27 12:57:11 8596 CHANGE USER BOILER PROPLUS BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-09-27 12:57:11 9372 CHANGE USER BOILER PROPLUS BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-09-27 12:57:11 9444 CHANGE USER BOILER PROPLUS BUS_COUPLER_01 Phoenix Contact Remote IO ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-09-27 12:57:10 1710 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-09-27 12:57:09 2578 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-09-27 12:57:09 3090 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2021-09-27 12:57:09 6560 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-09-27 12:57:07 1020 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-09-27 12:57:07 7575 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-09-27 12:57:07 7582 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-09-27 12:56:57 892 CHANGE USER BOILER PROPLUS PC_DI1 Phoenix Contact Digital in 1 ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-09-27 12:56:57 1039 CHANGE USER BOILER PROPLUS PC_DI1 Phoenix Contact Digital in 1 DISC_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-09-27 12:56:57 1980 ALARM PROCESS BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-09-27 12:56:55 7025 CHANGE USER BOILER PROPLUS PC_DI1 Phoenix Contact Digital in 1 DI1/SIMULATE_D.ENABLE ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-09-27 12:56:53 1981 ALARM PROCESS BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 DISC_ALM INACT/UNACK 11-WARNING DI_ALM Tripped