Event List (683298)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Office DeltaV 2021-11-02 11:21:17 5826 ALARM DEVICE AREA_A CNTRL01 PY101 COMM_ALM INACT/ACK 11-WARNING OK Communications failure
SHP Office DeltaV 2021-11-02 11:21:17 5826 ALARM DEVICE AREA_A CNTRL01 PY101 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2021-11-02 11:21:17 5826 ALARM DEVICE AREA_A CNTRL01 PY101 MAINT_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2021-11-02 11:21:17 5826 ALARM DEVICE AREA_A CNTRL01 PY101 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2021-11-02 11:21:17 5984 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-11-02 11:21:17 6430 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-11-02 11:21:17 7030 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2021-11-02 11:21:17 7830 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-11-02 11:21:16 9430 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-11-02 11:18:55 2630 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 11:18:16 3130 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-02 11:17:57 9330 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 11:15:03 7750 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-02 11:13:59 6990 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 11:11:55 730 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 11:11:13 4630 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 10:53:25 1260 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-02 10:53:13 1450 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:44:08 3930 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2021-11-02 10:43:57 1174 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:43:53 3530 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-02 10:43:43 1174 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:37:07 899 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/ACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:37:06 5080 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2021-11-02 10:37:06 7800 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2021-11-02 10:37:05 5300 CHANGE USER BOILER PROPLUS LS107 Boiler HIHI Level DISC_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-02 10:37:05 5391 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-02 10:37:05 5410 CHANGE USER AREA_A PROPLUS AS01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-02 10:37:05 5463 CHANGE USER BOILER PROPLUS XV110 Well Head Valve FAIL_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-02 10:37:05 5500 CHANGE USER AREA_A PROPLUS PROPLUS MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-02 10:37:05 7990 ALARM PROCESS BOILER CNTRL01 XV110 Well Head Valve FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2021-11-02 10:37:05 8993 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/ACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-11-02 10:34:37 9520 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-02 10:34:37 9620 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-02 10:34:22 7720 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:34:17 9220 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2021-11-02 10:34:17 9320 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-02 10:34:12 5050 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:34:12 5050 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM RECORD(S) LOST 4-INFO
SHP Office DeltaV 2021-11-02 10:34:06 7720 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-02 10:34:05 9850 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2021-11-02 10:34:02 3030 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-02 10:34:02 8420 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-02 10:33:49 1990 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-02 10:33:46 6220 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-02 10:28:45 580 CHANGE USER AREA_A PROPLUS LOGOFF <none>
SHP Office DeltaV 2021-11-02 10:28:45 3230 CHANGE USER AREA_A PROPLUS LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 10:25:47 7790 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2021-11-02 10:25:47 9040 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-02 10:25:32 0 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-02 10:25:16 961 EVENT SYSTEM AREA_A PROPLUS JOUR ACTIVE 4-INFO
SHP Office DeltaV 2021-11-01 17:23:27 470 CHANGE USER AREA_A PROPLUS LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 17:06:43 7580 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:44:54 9630 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:43:52 269 CHANGE USER BOILER PROPLUS PIC101 TIC102 Boiler temperature PID1/OUT.CV ADMINISTRATOR NEW VALUE = 50
SHP Office DeltaV 2021-11-01 16:43:48 8456 CHANGE USER BOILER PROPLUS PIC101 TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2021-11-01 16:43:27 730 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:42:36 2640 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:42:29 9300 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:41:47 2634 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:41:46 8665 CHANGE USER BOILER PROPLUS LS107 Boiler HIHI Level DISC_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:41:46 8692 CHANGE USER BOILER PROPLUS LS107 Boiler HIHI Level ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-11-01 16:41:23 1982 CHANGE USER BOILER PROPLUS PIC101 TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = AUTO
SHP Office DeltaV 2021-11-01 16:41:20 2624 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-11-01 16:41:10 2978 CHANGE USER BOILER PROPLUS PIC101 TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2021-11-01 16:40:58 3969 CHANGE USER BOILER PROPLUS ANALOG1 Phoenix Contact Analogue 1 PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:40:58 3999 CHANGE USER BOILER PROPLUS ANALOG1 Phoenix Contact Analogue 1 ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-11-01 16:40:58 9120 ALARM INSTRUMENT BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 PVBAD_ALM ACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:40:57 9602 CHANGE USER BOILER PROPLUS ANALOG1 Phoenix Contact Analogue 1 PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:40:57 9661 CHANGE USER BOILER PROPLUS ANALOG1 Phoenix Contact Analogue 1 ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-11-01 16:40:56 1794 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:40:56 1824 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:40:56 1920 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-11-01 16:40:55 5015 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:40:55 5108 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2021-11-01 16:40:55 5149 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-11-01 16:40:55 8602 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 515.669 Limit 300
SHP Office DeltaV 2021-11-01 16:40:55 8605 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:40:31 8589 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 316.038 Limit 300
SHP Office DeltaV 2021-11-01 16:40:27 8588 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 243.129 Limit 300
SHP Office DeltaV 2021-11-01 16:39:18 8543 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 459.974 Limit 300
SHP Office DeltaV 2021-11-01 16:35:20 2499 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:35:15 2500 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-11-01 16:35:03 7850 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:35:02 7860 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-11-01 16:34:52 2880 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-11-01 16:34:48 8730 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:34:44 1562 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2021-11-01 16:34:44 2032 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:34:37 2640 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:34:36 2677 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-11-01 16:34:36 4817 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Unavailable
SHP Office DeltaV 2021-11-01 16:34:36 4858 DOWNLOAD USER BOILER CNTRL01 LS107 Boiler HIHI Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2021-11-01 16:34:36 4961 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-11-01 16:34:36 9575 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Available
SHP Office DeltaV 2021-11-01 16:34:22 2490 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:34:10 6890 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:34:02 1090 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:32:23 6337 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:32:16 6326 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2021-11-01 16:32:01 6310 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:27:08 5520 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-11-01 16:27:02 2660 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-11-01 16:26:55 7450 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:26:46 5250 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-11-01 16:26:46 6810 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:26:39 4740 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:26:18 6170 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold restart on CNTRL01 failed; download items rejected
SHP Office DeltaV 2021-11-01 16:26:09 1930 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:25:52 9530 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2021-11-01 16:25:36 3240 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:24:00 5432 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Available
SHP Office DeltaV 2021-11-01 16:23:42 5310 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2021-11-01 16:23:41 1221 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 16:23:41 2825 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:41 5316 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2021-11-01 16:23:41 5318 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:41 6313 EVENT PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:41 8309 ALARM PROCESS BOILER CNTRL01 XV110 Well Head Valve FAIL_ALM INACT/UNACK 11-WARNING FAILED Clear
SHP Office DeltaV 2021-11-01 16:23:41 8852 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:41 8854 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:41 8854 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2021-11-01 16:23:40 1387 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2021-11-01 16:23:40 1478 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Unavailable
SHP Office DeltaV 2021-11-01 16:23:40 1813 ALARM PROCESS BOILER CNTRL01 F106 Combustion Air Fan FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2021-11-01 16:23:40 2824 EVENT PROCESS BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 ACTIVE 4-INFO PC_AO1/PID1 I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:40 2840 ALARM INSTRUMENT BOILER CNTRL01 PC_AO1 Phoenix Contact Analogue out 1 PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 3316 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:23:40 3319 ALARM INSTRUMENT BOILER CNTRL01 LS107 Boiler HIHI Level PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 3873 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 4307 ALARM PROCESS BOILER CNTRL01 F105 Boiler Feed Pump FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2021-11-01 16:23:40 5319 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:40 5320 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 Module Failure Active
SHP Office DeltaV 2021-11-01 16:23:40 5324 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/DI1 I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:40 5326 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 0 Limit 785
SHP Office DeltaV 2021-11-01 16:23:40 5328 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 750
SHP Office DeltaV 2021-11-01 16:23:40 5330 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 0 Limit 300
SHP Office DeltaV 2021-11-01 16:23:40 5331 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2021-11-01 16:23:40 5333 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2021-11-01 16:23:40 5334 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2021-11-01 16:23:40 5336 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 5824 EVENT PROCESS BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG1/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:40 5830 ALARM PROCESS BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 95
SHP Office DeltaV 2021-11-01 16:23:40 5832 ALARM PROCESS BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 90
SHP Office DeltaV 2021-11-01 16:23:40 5834 ALARM PROCESS BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 10
SHP Office DeltaV 2021-11-01 16:23:40 5835 ALARM PROCESS BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 5
SHP Office DeltaV 2021-11-01 16:23:40 5837 ALARM INSTRUMENT BOILER CNTRL01 ANALOG1 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 6320 EVENT PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature ACTIVE 4-INFO TIC102/PID1 I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:40 6325 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 0 Limit 80
SHP Office DeltaV 2021-11-01 16:23:40 6328 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature HI_ALM INACT/ACK 11-WARNING HIGH High Alarm Value 0 Limit 60
SHP Office DeltaV 2021-11-01 16:23:40 6329 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2021-11-01 16:23:40 6331 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2021-11-01 16:23:40 6333 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 20
SHP Office DeltaV 2021-11-01 16:23:40 6335 ALARM PROCESS BOILER CNTRL01 PIC101 TIC102 Boiler temperature DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 20
SHP Office DeltaV 2021-11-01 16:23:40 6337 ALARM INSTRUMENT BOILER CNTRL01 PIC101 TIC102 Boiler temperature PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 6826 ALARM PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 95
SHP Office DeltaV 2021-11-01 16:23:40 6828 ALARM PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 90
SHP Office DeltaV 2021-11-01 16:23:40 6830 ALARM PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 10
SHP Office DeltaV 2021-11-01 16:23:40 6832 ALARM PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 5
SHP Office DeltaV 2021-11-01 16:23:40 6834 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 7315 ALARM PROCESS BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:23:40 7317 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 7821 ALARM PROCESS BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2021-11-01 16:23:40 7823 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:40 8309 ALARM PROCESS BOILER CNTRL01 XV110 Well Head Valve FAIL_ALM ACT/UNACK 11-WARNING FAILED CLOSED confirm lost
SHP Office DeltaV 2021-11-01 16:23:40 8854 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 I/O Input Failure
SHP Office DeltaV 2021-11-01 16:23:40 8856 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 Module Failure Active
SHP Office DeltaV 2021-11-01 16:23:40 8858 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 8
SHP Office DeltaV 2021-11-01 16:23:40 8859 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 4
SHP Office DeltaV 2021-11-01 16:23:40 8861 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2021-11-01 16:23:40 8863 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2021-11-01 16:23:40 8864 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2021-11-01 16:23:40 8866 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2021-11-01 16:23:40 8867 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2021-11-01 16:23:38 6469 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2021-11-01 16:23:37 1212 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2021-11-01 16:23:37 1215 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 16:23:37 1218 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2021-11-01 16:23:36 7619 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 COMM_ALM INACT/ACK 11-WARNING OK Communications failure
SHP Office DeltaV 2021-11-01 16:23:36 7619 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2021-11-01 16:23:36 7619 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 MAINT_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2021-11-01 16:23:36 7619 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2021-11-01 16:23:33 6082 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2021-11-01 16:23:33 6982 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2021-11-01 16:23:33 7417 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2021-11-01 16:23:09 1217 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 16:23:06 9739 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Available
SHP Office DeltaV 2021-11-01 16:23:04 2860 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold restart on CNTRL01 failed; start download refused
SHP Office DeltaV 2021-11-01 16:22:49 1220 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]Redundancy: Standby Unavailable
SHP Office DeltaV 2021-11-01 16:22:43 7400 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:22:26 1440 CHANGE USER AREA_A PROPLUS LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 16:22:25 9250 CHANGE USER AREA_A PROPLUS LOGOFF <none>
SHP Office DeltaV 2021-11-01 16:22:17 2200 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2021-11-01 16:22:13 2740 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold restart on CNTRL01 failed; start download refused
SHP Office DeltaV 2021-11-01 16:21:47 5880 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 16:21:39 1349 EVENT SYSTEM AREA_A CNTRL01 REDU BKUPFAIL 00-80-74-01-ED-22 Standby Not Present Timeout
SHP Office DeltaV 2021-11-01 16:21:32 565 EVENT SYSTEM AREA_A PROPLUS JOUR ACTIVE 4-INFO
SHP Office DeltaV 2021-11-01 16:20:49 1226 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 16:19:39 2884 EVENT SYSTEM AREA_A CNTRL01 REDU BKUPFAIL 00-80-74-01-ED-22 Standby Start of Download Timeout
SHP Office DeltaV 2021-11-01 16:18:49 1234 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]Redundancy: Standby Unavailable
SHP Office DeltaV 2021-11-01 16:05:52 5050 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 16:05:35 4060 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 16:03:04 250 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 16:02:46 9260 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 16:00:15 5450 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 15:59:58 4460 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 15:58:20 5040 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2021-11-01 15:58:20 6760 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2021-11-01 15:57:27 4450 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 15:57:09 9650 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 15:55:13 7760 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 15:54:58 753 EVENT SYSTEM AREA_A PROPLUS JOUR ACTIVE 4-INFO
SHP Office DeltaV 2021-11-01 10:29:30 3350 CHANGE USER AREA_A PROPLUS LOGOFF ADMINISTRATOR
SHP Office DeltaV 2021-11-01 10:20:41 9368 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 10:20:40 1220 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-01 10:20:25 830 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 10:20:25 9362 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 10:04:41 8898 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 10:04:25 8891 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 09:48:55 8435 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 09:48:41 8426 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 09:48:35 2980 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 09:48:34 7110 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 09:48:34 8610 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 09:48:33 5510 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 09:25:41 7745 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 09:25:25 7738 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 09:25:11 7733 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-11-01 09:17:25 7511 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 09:17:11 7501 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 09:01:11 7026 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 09:00:55 7020 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 09:00:52 208 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 09:00:52 741 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 09:00:51 7590 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 08:52:55 6783 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 08:52:41 6773 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 08:52:30 9990 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 08:52:29 1954 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-01 08:52:29 1959 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-11-01 08:36:11 6288 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 08:35:55 6277 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 08:35:53 5340 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 08:35:53 6590 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 08:27:55 6044 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 08:27:41 6038 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 08:27:34 3210 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 08:27:34 3340 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-11-01 08:27:33 1221 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-01 08:27:33 1227 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-11-01 08:27:33 1232 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 08:27:32 4490 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 08:27:32 4620 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 08:19:41 5797 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 08:19:25 5787 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 07:54:41 5044 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 07:54:25 5039 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 07:37:55 4571 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 07:37:41 4565 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 07:29:25 4316 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 07:29:11 4309 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 07:29:05 5770 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 07:29:04 9494 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-01 07:29:04 9499 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-11-01 07:21:11 4067 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 07:21:00 8257 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 07:20:55 4062 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 07:12:55 3824 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 07:12:41 3814 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 07:12:25 3808 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-11-01 06:31:11 2589 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 06:30:55 2584 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 05:57:55 1608 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 05:57:41 1600 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 05:57:37 9600 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 05:41:25 1114 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 05:41:11 1111 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 05:41:02 4910 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 04:52:24 9674 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 04:52:10 9664 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 04:44:10 9432 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 04:43:54 9424 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 04:03:24 8229 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 04:03:10 8222 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 04:02:58 2120 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 04:02:57 3401 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-11-01 04:02:57 3406 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-01 03:47:10 7751 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 03:47:08 9980 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-01 03:46:53 9600 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 03:46:52 3438 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 03:46:52 3446 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 03:46:40 7738 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 03:46:36 1600 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 03:38:48 2540 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-01 03:38:40 7497 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 03:38:31 9689 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 03:38:31 9830 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 03:38:24 7494 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 03:30:24 7256 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 03:30:15 7000 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-01 03:30:10 7253 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 03:30:00 6610 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 03:22:10 7013 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 03:21:54 7007 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 03:21:40 7002 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-11-01 03:13:40 6764 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 03:13:24 6755 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 02:56:54 6256 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 02:56:40 6250 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 02:40:24 5753 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 02:40:10 5748 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 02:23:54 5248 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 02:23:40 5240 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 02:15:54 5004 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 02:15:40 4999 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 02:07:40 4742 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 02:07:24 4740 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 02:07:09 9925 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-01 02:07:09 9931 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-11-01 01:51:10 4261 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 01:50:54 4250 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 01:50:48 8936 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 01:34:54 3764 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 01:34:40 3756 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 01:34:31 6170 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-11-01 01:18:40 3269 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 01:18:24 3264 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 01:18:10 3254 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-11-01 01:18:09 3442 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 01:18:07 8441 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-11-01 01:18:07 8446 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-11-01 01:18:07 8452 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 01:10:33 4360 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-01 01:10:24 3017 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 01:10:18 4130 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 01:10:17 8206 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 01:10:10 3009 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 01:02:10 2763 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 01:02:08 2610 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-11-01 01:01:54 2753 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 01:01:53 2380 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-11-01 01:01:49 6439 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 01:01:49 6444 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 00:53:54 2520 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 00:53:40 2513 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 00:53:32 5197 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-11-01 00:53:32 6197 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-11-01 00:45:40 2264 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 00:45:24 2261 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 00:37:40 2032 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 00:37:24 2026 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 00:37:10 2018 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-11-01 00:21:10 1521 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 00:20:54 1513 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 00:13:10 1284 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 00:12:54 1275 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-11-01 00:04:54 1022 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-11-01 00:04:40 1014 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 23:48:40 536 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 23:48:24 528 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 23:48:10 524 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 23:48:07 5246 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 23:15:53 9551 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 23:15:39 9543 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:59:39 9057 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:59:23 9049 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:51:39 8815 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:51:23 8805 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:43:34 9190 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-10-31 22:43:23 8551 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:43:19 8960 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-10-31 22:43:18 1743 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 22:43:09 8542 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:35:23 8319 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:35:09 8308 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:34:53 8298 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 22:34:52 6310 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-10-31 22:27:09 8065 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:27:04 7550 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-10-31 22:26:53 8058 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:26:49 7320 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-10-31 22:19:09 7825 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:18:53 7817 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 22:02:53 7334 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 22:02:39 7326 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 21:46:39 6841 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 21:46:23 6830 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 21:38:23 6605 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 21:38:09 6595 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 21:30:23 6346 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 21:30:09 6341 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 21:22:09 6094 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 21:22:06 9288 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 21:21:53 6092 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 21:21:50 771 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 21:21:50 775 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 21:14:09 5859 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 21:13:53 5850 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 21:13:39 5846 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 21:05:53 5608 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 21:05:39 5597 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 20:57:39 5365 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 20:57:38 5360 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-10-31 20:57:23 4820 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-10-31 20:57:23 5358 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 20:33:09 4611 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 20:32:53 4607 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 20:24:53 4351 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 20:24:39 4339 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 20:24:35 7528 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 20:24:35 8059 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 20:00:39 3631 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 20:00:37 3430 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-10-31 20:00:23 3623 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 20:00:22 3200 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-10-31 19:44:23 3126 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 19:44:09 3124 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 19:44:00 311 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 19:44:00 6313 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 19:12:09 2167 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 19:11:53 2161 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 19:11:49 9070 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-10-31 19:11:48 350 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-10-31 19:11:48 3347 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 19:11:48 3351 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 19:04:09 1928 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 19:03:53 1919 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 18:56:09 1680 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 18:55:53 1678 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 18:55:39 1675 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 18:47:53 1436 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 18:47:39 1427 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 18:39:39 1180 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 18:39:23 1171 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 18:31:23 944 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 18:31:09 936 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:58:52 9968 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:58:38 9959 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:58:27 3641 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 17:58:27 3645 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 17:50:38 9716 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:50:22 9708 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:42:22 9465 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:42:08 9454 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:34:22 9215 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:34:09 9950 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-10-31 17:34:08 9206 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:33:54 9410 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-10-31 17:33:52 9200 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 17:33:51 3886 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 17:33:51 3890 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 17:25:52 8970 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:25:38 8964 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:09:38 8486 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:09:22 8482 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:01:22 8237 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 17:01:06 8229 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 17:00:57 3414 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2021-10-31 17:00:57 3420 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-10-31 16:12:22 6764 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 16:12:06 6755 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 16:04:06 6519 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 16:03:52 6510 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 16:03:45 9697 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 16:03:45 9701 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 15:55:52 6272 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 15:55:36 6269 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 15:14:52 5041 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 15:14:36 5035 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 15:06:36 4788 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 15:06:22 4777 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 14:58:27 5040 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2021-10-31 14:58:22 4552 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 14:58:12 4810 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2021-10-31 14:58:11 8238 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 14:58:06 4544 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 14:17:22 3328 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 14:17:06 3322 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 14:16:52 3313 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 13:52:52 2594 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 13:52:36 2587 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 13:52:22 2579 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2021-10-31 13:44:36 2348 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 13:44:22 2338 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 13:36:22 2091 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 13:36:06 2081 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 13:19:52 1609 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 13:19:36 1601 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 13:19:25 5830 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-10-31 13:19:24 7783 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 13:19:23 7110 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-10-31 13:11:22 1353 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2021-10-31 13:11:06 1344 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2021-10-31 13:11:04 730 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2021-10-31 13:11:04 1533 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2021-10-31 13:11:02 2010 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2021-10-31 13:11:02 6029 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2021-10-31 13:11:02 6567 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2021-10-31 13:03:06 1098 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network