System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Office DeltaV 2022-11-07 10:26:00 6200 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-07 10:26:00 8025 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-07 10:26:00 8209 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 10:25:58 3242 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-07 10:25:58 3245 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 09:25:48 1216 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-07 09:25:37 3404 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-07 09:25:32 1217 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-07 09:25:32 1404 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 09:25:29 6404 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 09:25:25 6405 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-07 09:17:32 3084 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-07 09:17:27 1082 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 09:17:22 6080 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 09:17:21 6081 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-07 09:16:07 3071 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-07 09:15:57 1073 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 09:15:56 6073 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-07 09:15:56 6080 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 08:26:10 110 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-11-07 08:26:06 1580 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-07 08:26:06 9864 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 08:26:02 1863 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-07 08:26:01 9674 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-07 08:25:58 7740 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-07 08:25:54 9720 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-11-07 08:25:47 9667 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-07 08:25:45 8150 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-07 08:25:41 3730 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-07 08:25:41 4856 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-07 08:25:41 4859 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 08:25:02 1853 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-07 08:25:01 9853 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-07 08:24:51 4852 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-07 08:24:51 4855 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Unit DeltaV 2022-11-07 00:40:16 1435 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-11-07 00:40:07 5167 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-11-07 00:39:47 5164 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-11-07 00:39:40 5150 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-11-06 13:37:13 8420 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-11-05 21:35:02 8 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:02 7016 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2022-11-05 21:35:02 7018 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:01 8 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:01 3530 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:01 7014 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2022-11-05 21:35:01 7020 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:01 9518 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:00 3530 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:35:00 9518 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:15 6980 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2022-11-05 21:32:15 6981 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:14 3494 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:14 6975 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2022-11-05 21:32:14 6982 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:14 9482 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:14 9972 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:13 3492 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:13 9483 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 21:32:13 9974 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:08 961 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2022-11-05 17:30:08 963 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:07 953 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2022-11-05 17:30:07 960 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:07 3462 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:07 3949 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:06 3459 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:06 3949 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:06 7474 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-11-05 17:30:05 7470 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2022-11-05 00:19:51 1462 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-11-05 00:19:45 5589 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-11-05 00:19:25 5589 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-11-05 00:19:15 5178 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2022-11-04 15:04:38 2142 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 15:04:35 7141 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 14:16:38 924 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 14:16:37 5924 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 13:26:14 144 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 13:26:11 5143 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 12:40:09 549 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-04 12:39:58 3547 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-04 12:39:58 8547 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 12:39:54 3546 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 09:32:47 3874 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 09:32:43 8876 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 08:59:47 3076 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-04 08:59:44 8073 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Unit DeltaV 2022-11-04 07:54:08 5824 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-11-04 07:54:04 9380 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-11-04 07:53:34 9364 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-11-04 07:53:32 9561 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2022-11-03 15:18:13 6612 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 15:18:12 1612 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 12:55:54 5011 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-03 12:55:43 8016 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-03 10:53:42 185 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 10:53:40 5184 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 10:07:57 817 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-03 10:07:51 8813 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 10:07:49 3811 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 10:07:46 8809 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 10:07:45 3808 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-03 10:07:45 3814 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Unit DeltaV 2022-11-03 10:06:23 890 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-11-03 09:18:01 7645 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 09:17:59 2645 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 09:01:41 7192 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 09:01:38 2191 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 08:42:56 6773 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-03 08:42:54 1773 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 14:50:08 3610 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 14:50:07 5110 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 13:35:28 8275 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 13:35:27 3276 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 12:59:18 9499 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-02 12:59:08 2496 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-02 12:07:29 2200 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-11-02 12:07:29 5875 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-11-02 12:07:20 5690 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-11-02 12:02:02 9470 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-11-02 11:00:01 4414 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 11:00:01 6414 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-02 10:59:59 1800 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-11-02 10:59:58 9415 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-02 10:59:58 9419 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:46 5690 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 10:59:46 6412 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-02 10:59:44 1420 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-11-02 10:59:43 5660 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 10:59:41 4219 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-02 10:59:41 4407 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:37 9405 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:36 4403 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:35 9190 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 10:59:33 9401 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:26 4397 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:25 2820 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 10:59:25 4211 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-02 10:59:24 9396 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:21 4394 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:18 6050 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 10:59:16 9390 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:59:15 9390 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-02 10:59:05 8760 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-02 10:58:12 9870 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-11-02 10:57:57 9630 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-11-02 10:57:55 4165 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-02 10:57:46 4351 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:46 6351 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-02 10:57:42 9352 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:41 4163 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-11-02 10:57:41 4353 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:38 852 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:36 4352 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:35 9352 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-02 10:57:33 2852 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:31 4352 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:31 6352 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-02 10:57:28 4854 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:26 9353 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-02 10:57:21 4354 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-02 10:57:19 9354 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 16:37:09 6550 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-11-01 16:36:58 3240 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-11-01 13:16:02 5427 CHANGE USER BOILER PROPLUS F106 Combustion Air Fan DC1/SP_D.CV ADMINISTRATOR NEW VALUE = STOP
SHP Office DeltaV 2022-11-01 13:15:57 2001 CHANGE USER BOILER PROPLUS LS107 Boiler HIHI Level DISC_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-11-01 13:15:57 2073 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-11-01 13:15:57 3323 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2022-11-01 13:15:57 9818 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 524.705 Limit 300
SHP Office DeltaV 2022-11-01 12:54:27 80 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-11-01 12:54:25 7570 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-11-01 12:53:48 3729 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-01 12:53:36 6723 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-01 11:53:33 3009 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2022-11-01 11:53:16 7008 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2022-11-01 11:41:51 1786 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-11-01 11:41:50 9786 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 11:41:48 4787 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-11-01 11:41:47 4786 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 11:38:00 9708 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 11:37:59 2709 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 11:25:07 8286 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/UNACK 11-WARNING DI_ALM High Level
SHP Office DeltaV 2022-11-01 11:24:38 6267 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM ACT/UNACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2022-11-01 11:24:34 6759 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 427.667 Limit 300
SHP Office DeltaV 2022-11-01 11:24:31 6757 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 253.381 Limit 300
SHP Office DeltaV 2022-11-01 11:23:45 9437 CHANGE USER BOILER PROPLUS F106 Combustion Air Fan DC1/SP_D.CV ADMINISTRATOR NEW VALUE = START
SHP Office DeltaV 2022-11-01 09:13:40 6137 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 09:13:37 1133 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 09:13:00 6088 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-11-01 09:12:57 1083 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 17:07:36 5030 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 17:07:08 3000 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2022-10-31 17:06:54 3420 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2022-10-31 17:06:51 9580 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2022-10-31 17:06:41 350 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2022-10-31 16:57:36 1490 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:57:36 1600 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:57:29 320 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:57:28 8370 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:49:40 4270 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:44:48 6015 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-09-AA Standby is now Available
SHP Office DeltaV 2022-10-31 16:44:47 1481 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-09-AA Standby is now Unavailable
SHP Office DeltaV 2022-10-31 16:44:47 1622 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2022-10-31 16:44:44 1979 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2022-10-31 16:44:44 2959 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2022-10-31 16:44:44 3222 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2022-10-31 16:43:27 460 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-31 16:42:56 9770 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: NO CONFIGURATION
SHP Office DeltaV 2022-10-31 16:42:49 5260 DOWNLOAD USER AREA_A AS01 AS01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2022-10-31 16:42:48 900 DOWNLOAD USER AREA_A AS01 AS01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2022-10-31 16:42:48 7850 ALARM HARDWARE AREA_A AS01 AS01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 16:42:48 7850 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 16:42:48 7850 ALARM HARDWARE AREA_A AS01 AS01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2022-10-31 16:42:14 630 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:42:13 9060 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-31 16:41:11 6350 STATUS SYSTEM AREA_A PROPLUS AS01 NO CONFIGURATION 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-31 16:32:04 7780 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: NO CONFIGURATION
SHP Office DeltaV 2022-10-31 16:31:34 3720 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 16:31:34 6720 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 16:31:33 3220 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 16:27:39 3520 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-31 16:27:39 6490 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:27:26 9260 STATUS SYSTEM AREA_A PROPLUS AS01 NO CONFIGURATION 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-31 16:26:31 1150 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: NO CONFIGURATION
SHP Office DeltaV 2022-10-31 16:26:13 6540 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 16:26:12 1540 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 16:25:51 7730 CHANGE USER AREA_A AS01 LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:23:23 7410 ALARM HARDWARE AREA_A AS01 AS01 FAILED_ALM ACT/UNACK 12-CRITICAL FAILED Node: Node not configured
SHP Office DeltaV 2022-10-31 16:20:03 6540 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:19:15 210 STATUS SYSTEM AREA_A PROPLUS AS01 NO CONFIGURATION 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-31 16:19:12 4740 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-31 16:19:12 6610 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:18:42 1203 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 16:17:53 5770 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-31 16:17:35 8230 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 16:17:34 3230 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 16:17:27 1154 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 16:17:25 6165 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 16:14:41 1440 CHANGE USER AREA_A AS01 LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 16:14:39 2250 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 14:27:45 3430 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-10-31 14:27:42 7930 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2022-10-31 13:28:27 6838 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 13:28:26 1837 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 13:27:27 6797 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 13:27:25 1795 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 13:25:12 4747 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 13:25:02 1744 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 12:39:41 2843 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 12:39:31 4842 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 12:39:30 9843 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 12:39:29 9843 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 12:36:51 2852 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 12:36:41 4849 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 12:36:40 9849 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 12:36:40 9852 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 12:27:05 4170 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 12:27:03 8260 CHANGE USER AREA_A PROPLUS AS01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-31 11:09:47 5983 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 11:09:47 7981 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 11:09:46 2981 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 11:09:46 2987 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 11:07:57 5944 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 11:07:57 7943 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 11:07:56 2942 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 11:07:56 2948 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-31 10:15:07 3030 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 10:15:00 800 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-31 10:14:42 8890 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2022-10-31 10:13:35 2590 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-31 10:13:35 4150 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 10:13:29 9170 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-31 10:13:13 8770 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2022-10-31 09:50:55 2490 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-31 09:50:25 490 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 09:50:25 1490 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 09:50:23 6490 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 09:50:18 5911 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 09:50:17 910 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 09:50:01 8710 CHANGE USER AREA_A AS01 LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:49:58 540 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:41:23 1920 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:41:20 9550 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-31 09:41:09 890 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-31 09:41:09 2300 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:41:05 9350 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-31 09:40:50 9050 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-31 09:40:43 580 DOWNLOAD USER AREA_A AS01 AS01 UPDATE COLD_RESTART End of download. - 0
SHP Office DeltaV 2022-10-31 09:40:41 1550 DOWNLOAD USER AREA_A AS01 AS01 UPDATE COLD_RESTART Start of Download - 0
SHP Office DeltaV 2022-10-31 09:40:41 9040 ALARM HARDWARE AREA_A AS01 AS01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 09:40:41 9040 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 09:40:41 9040 ALARM HARDWARE AREA_A AS01 AS01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2022-10-31 09:40:25 3950 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-31 09:39:55 450 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 09:39:55 2950 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 09:39:54 1450 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 09:39:47 5655 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 09:39:46 653 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 09:39:31 3230 CHANGE USER AREA_A AS01 LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:30:41 8020 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:30:28 7600 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-31 09:30:28 9160 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:29:51 3020 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-31 09:29:36 2420 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: NO CONFIGURATION
SHP Office DeltaV 2022-10-31 09:29:06 2120 STATUS SYSTEM AREA_A PROPLUS AS01 NO CONFIGURATION 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-31 09:29:05 4670 DOWNLOAD USER AREA_A AS01 AS01 UPDATE COLD_RESTART End of download. - 0
SHP Office DeltaV 2022-10-31 09:29:05 7790 ALARM HARDWARE AREA_A AS01 AS01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 09:29:05 7790 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-31 09:29:05 7790 ALARM HARDWARE AREA_A AS01 AS01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2022-10-31 09:28:56 2630 DOWNLOAD USER AREA_A AS01 AS01 UPDATE COLD_RESTART Start of Download - 0
SHP Office DeltaV 2022-10-31 09:28:55 8260 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - ID = 2622816257
SHP Office DeltaV 2022-10-31 09:28:53 8420 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-31 09:28:36 6320 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-31 09:28:28 7620 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:28:26 9420 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:28:06 5420 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 09:28:05 420 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 09:28:05 5291 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-31 09:28:04 291 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-31 09:27:46 6070 CHANGE USER AREA_A AS01 LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-31 09:27:36 8730 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Unit DeltaV 2022-10-28 15:26:53 515 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-28 15:26:48 3533 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 15:26:28 3527 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 15:26:17 4120 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-28 15:17:32 6169 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-28 15:17:28 3466 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 15:16:58 3459 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 15:16:56 9848 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2022-10-28 13:33:06 3106 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2022-10-28 13:33:06 7130 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 661.011 Limit 785
SHP Office DeltaV 2022-10-28 13:33:06 7132 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 661.011 Limit 300
SHP Office DeltaV 2022-10-28 13:33:05 9063 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2022-10-28 13:33:05 9107 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level HI_HI_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:33:05 9155 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:32:38 7119 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM INACT/UNACK 15-CRITICAL HIHI High High Alarm Value 711.175 Limit 785
SHP Office DeltaV 2022-10-28 13:32:14 7107 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM ACT/UNACK 15-CRITICAL HIHI High High Alarm Value 804.065 Limit 785
SHP Office DeltaV 2022-10-28 13:32:09 7104 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 387.899 Limit 300
SHP Office DeltaV 2022-10-28 13:31:48 7097 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 267.185 Limit 300
SHP Office DeltaV 2022-10-28 13:31:03 9718 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/OUT.CV ADMINISTRATOR NEW VALUE = 20
SHP Office DeltaV 2022-10-28 13:30:39 1731 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2022-10-28 13:30:37 4643 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = AUTO
SHP Office DeltaV 2022-10-28 13:30:34 1476 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2022-10-28 13:30:19 7780 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-28 13:29:47 4680 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-28 13:28:53 8280 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-28 13:28:52 1530 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-28 13:28:52 2020 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-28 13:28:52 2774 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:52 2780 CHANGE USER AREA_A PROPLUS PROPLUS MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:52 5544 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-28 13:28:52 5774 CHANGE USER BOILER PROPLUS LS107 Boiler HIHI Level DISC_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:52 5825 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:52 6523 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2022-10-28 13:28:52 7019 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 398.437 Limit 300
SHP Office DeltaV 2022-10-28 13:28:52 9427 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-28 13:28:51 477 CHANGE USER BOILER PROPLUS ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:51 3679 CHANGE USER BOILER PROPLUS PC_DI2 Phoenix Contact Digital in 1 PV_BAD.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:51 6788 CHANGE USER BOILER PROPLUS PC_DI1 Phoenix Contact Digital in 1 PV_BAD.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:51 9028 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-28 13:28:51 9775 CHANGE USER BOILER PROPLUS BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2022-10-28 13:28:29 7005 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 315.18 Limit 300
SHP Office DeltaV 2022-10-28 13:28:27 7004 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 296.75 Limit 300
SHP Unit DeltaV 2022-10-28 10:47:57 3977 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-28 10:47:48 3262 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 10:47:28 3160 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 10:47:21 7413 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-28 06:26:19 7512 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-28 06:26:08 3289 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 06:25:48 3279 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-28 06:25:44 1166 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2022-10-27 12:12:47 7360 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-27 12:12:42 6390 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-27 12:12:12 1410 CHANGE USER AREA_A AS01 LOGOFF <none>
SHP Office DeltaV 2022-10-27 12:12:12 2500 CHANGE USER AREA_A AS01 LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-27 12:12:02 6460 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-27 12:11:45 1360 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-27 12:11:44 8050 ALARM HARDWARE AREA_A AS01 AS01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-27 12:11:44 8050 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2022-10-27 12:11:44 8050 ALARM HARDWARE AREA_A AS01 AS01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2022-10-27 12:11:43 4330 DOWNLOAD USER AREA_A AS01 AS01 UPDATE COLD_RESTART End of download. - 0
SHP Office DeltaV 2022-10-27 12:11:42 2630 DOWNLOAD USER AREA_A AS01 AS01 UPDATE COLD_RESTART Start of Download - 0
SHP Office DeltaV 2022-10-27 12:11:37 8560 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-27 12:11:36 1790 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - ID = 2622816259
SHP Office DeltaV 2022-10-27 12:11:36 4910 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - ID = 2622816257
SHP Office DeltaV 2022-10-27 12:11:19 60 STATUS SYSTEM AREA_A PROPLUS AS01 NOT COMMUNICATING 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-27 12:11:12 1860 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-27 12:11:08 3360 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-27 12:10:48 830 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-27 12:10:48 9060 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-27 12:10:47 4060 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-27 12:10:46 5828 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-27 12:10:32 1210 CHANGE USER AREA_A AS01 LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-27 12:10:28 8290 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Unit DeltaV 2022-10-26 16:06:30 8909 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-26 16:06:26 3626 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-26 16:05:56 3628 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-26 16:05:55 2517 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-25 10:06:42 2680 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Unit DeltaV 2022-10-25 10:06:11 5250 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-25 08:59:28 1582 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-25 08:59:24 2074 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-25 08:31:27 9470 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2022-10-25 08:30:39 4240 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-25 08:29:08 3310 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-25 08:29:08 3310 STATUS SYSTEM AREA_A PROPLUS AS01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-25 08:29:08 3310 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-25 08:29:07 9208 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-25 08:28:58 2970 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-10-25 08:28:58 4520 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-25 08:28:54 6110 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-25 08:28:52 8310 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-25 08:28:50 4706 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-25 08:28:49 1240 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-25 08:28:48 9840 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-25 08:28:46 9704 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-25 08:28:45 4704 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2022-10-25 08:28:42 9310 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2022-10-25 08:28:38 1210 STATUS SYSTEM AREA_A PROPLUS AS01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-25 08:28:23 990 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-25 08:28:18 9850 ALARM HARDWARE AREA_A AS01 AS01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-25 08:28:08 6170 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-25 08:28:07 5270 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2022-10-25 08:28:06 9420 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2022-10-24 12:59:55 3640 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2022-10-24 12:59:41 5485 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-24 12:59:40 3140 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2022-10-24 12:59:27 5490 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2022-10-24 12:59:25 2140 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2022-10-24 12:59:19 176 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2022-10-24 12:59:17 679 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Office DeltaV 2022-10-24 12:09:54 2949 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - AS01
SHP Office DeltaV 2022-10-24 12:09:52 9449 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Unit DeltaV 2022-10-24 11:25:10 6939 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-24 11:25:10 6939 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-24 11:25:04 2434 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-24 11:25:04 2434 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-24 11:24:44 2429 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-24 11:24:44 2429 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-24 11:24:35 522 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-24 11:24:35 522 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-24 09:44:21 9716 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-24 09:44:14 1702 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-24 09:43:54 1694 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-24 09:43:46 3083 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-23 11:00:09 957 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-23 11:00:02 7976 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-23 10:59:42 7969 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-23 10:59:33 4560 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-23 00:36:23 6195 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-23 00:36:12 3732 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-23 00:35:52 3738 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-23 00:35:47 9730 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-22 22:38:21 6229 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-22 22:38:12 6929 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 22:37:52 6918 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 22:37:45 9405 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2022-10-22 15:47:36 352 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:36 843 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:36 7851 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2022-10-22 15:47:36 7853 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:35 4363 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:34 351 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:34 841 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:34 7845 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2022-10-22 15:47:34 7851 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:47:33 4364 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:19 329 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:19 819 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:19 7830 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2022-10-22 15:46:19 7832 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:18 330 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:18 821 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:18 4344 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:18 7824 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2022-10-22 15:46:18 7831 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-22 15:46:17 4340 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2022-10-22 13:59:28 4127 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-22 13:59:22 3457 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 13:59:02 3455 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 13:58:52 7449 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-22 12:08:51 3743 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-22 12:08:42 2721 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 12:08:22 2708 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 12:08:15 7301 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-22 10:02:55 6479 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-22 10:02:52 1895 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 10:02:22 1891 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-22 10:02:19 9881 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-21 14:15:18 5948 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2022-10-21 14:15:11 6982 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-21 14:14:51 6973 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2022-10-21 14:14:42 9459 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2022-10-21 11:27:17 1810 CHANGE USER AREA_A AS01 REMOTE LOGON ADMINISTRATOR
SHP Unit DeltaV 2022-10-21 11:26:45 3970 CHANGE USER AREA_A AS01 REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2022-10-20 09:14:09 6378 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2022-10-20 09:14:09 6379 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-20 09:14:08 2896 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2022-10-20 09:14:08 8879 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure