Event List (685884)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Unit DeltaV 2016-05-15 05:30:39 3897 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:30:33 7406 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:30:18 6403 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:29:52 7405 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:28:44 7403 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:28:24 6398 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:28:23 7401 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:26:52 6397 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:26:33 6396 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:26:12 7884 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:26:10 3430 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:25:17 7881 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:24:09 6884 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:23:54 3886 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:23:54 3887 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:23:54 6885 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:23:53 3888 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:23:34 3888 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:23:34 3889 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 05:23:33 3889 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:23:21 8630 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:21:31 6876 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:20:29 6876 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:19:55 3881 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:19:55 3883 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:19:54 3880 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:19:35 3882 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:19:35 3883 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 05:19:34 3879 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:19:17 6386 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:19:12 2391 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 05:19:08 2391 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 05:18:18 6877 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:18:09 8630 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:16:53 6875 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:16:36 3877 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:16:36 3879 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:16:35 3879 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:16:35 6386 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:16:11 7878 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:15:56 3878 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:15:56 3879 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 05:15:55 3878 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:15:21 3830 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:14:45 6382 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:14:25 6382 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:14:16 3874 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:14:16 3875 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:14:15 3876 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:13:47 7871 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:13:10 3875 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:13:10 3876 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 05:13:09 3876 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:11:27 6381 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:11:11 7870 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:10:23 7377 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:10:09 3820 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:09:37 7379 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:08:55 6373 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:08:17 7865 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:07:40 3862 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:07:40 3864 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:07:39 3865 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:07:20 3862 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:07:20 3864 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 05:07:20 9020 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:07:19 3862 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:07:03 7862 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:06:20 6371 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:05:57 3858 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:05:57 3859 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:05:56 3861 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:05:37 6367 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:05:34 7857 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:05:22 3858 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:05:22 3859 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 05:05:21 3859 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:03:36 7372 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:02:36 6369 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:02:36 7373 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:02:08 9010 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 05:01:59 7858 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:01:30 7859 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:01:19 3858 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 05:01:19 3860 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 05:01:18 3860 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 05:01:18 6367 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:59:20 4210 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:59:09 3853 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:59:09 3854 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:59:08 3853 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:58:33 3843 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:58:33 3845 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:58:32 3846 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:57:39 3841 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:57:39 3842 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:57:38 3839 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:57:32 6837 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:57:02 6839 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:56:58 7841 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:56:43 6351 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:56:20 3843 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:56:20 3845 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:56:19 3846 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:56:04 3849 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:56:04 3851 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:56:03 3851 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:55:48 6355 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:55:19 7353 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:54:08 4200 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:53:37 7354 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:53:21 7834 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:52:21 6829 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:51:39 7351 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:51:21 7351 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:51:19 9410 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:50:55 7836 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:49:57 7836 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:49:56 6832 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:49:54 3835 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:49:54 3837 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:49:53 3837 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:49:28 7349 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:49:05 6341 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:48:13 3833 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:48:13 3834 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:48:12 3834 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:48:12 7345 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:48:09 6340 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:47:06 6342 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:46:35 6342 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:46:25 7834 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:46:07 7833 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:46:07 9400 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:45:26 6339 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:43:33 6333 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:43:19 4600 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:42:28 6819 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:42:09 3822 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:42:09 3824 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:42:08 3824 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:41:49 3820 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:41:49 3822 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:41:48 3821 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:40:50 6822 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:40:21 7332 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:39:07 6331 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:38:50 6331 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:38:22 7335 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:38:14 7822 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:38:07 4590 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:37:56 3828 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:37:56 3829 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:37:55 3830 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:37:33 3830 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:37:33 3832 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:37:32 3831 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:37:16 7828 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:35:39 7334 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:35:18 9780 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:35:00 7331 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:34:00 6335 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:33:30 6345 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:33:14 6830 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:32:29 6815 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:32:23 6327 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:31:16 7327 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:30:56 7814 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:30:35 7330 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:30:06 9790 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:30:04 6326 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:30:00 6816 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:28:19 6811 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:27:55 7323 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:27:18 4990 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:27:17 7812 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:24:54 7806 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:24:04 3804 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:24:04 3806 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:24:03 3808 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:23:11 3803 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:23:11 3805 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:23:10 3804 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:22:33 7311 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:22:06 4980 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:20:43 7804 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:19:42 6311 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:19:27 6313 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:19:18 180 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:18:57 7311 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:17:55 7309 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:17:38 6795 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:17:01 6792 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:16:48 6307 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:16:33 3800 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:16:33 3801 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:16:32 3803 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:15:27 6310 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:15:23 6799 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:14:37 3799 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:14:37 3800 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:14:36 3799 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:14:27 7310 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:14:06 180 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:13:21 6794 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:12:42 7305 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:12:19 3794 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:12:19 3796 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 04:12:18 3797 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:11:38 6792 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:11:17 5370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:11:06 3796 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 04:11:06 3797 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 04:11:05 3796 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:10:34 6299 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:10:07 6789 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:09:26 7301 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:08:21 6786 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:08:06 6786 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:07:55 7300 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:07:35 7786 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:06:34 6290 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:06:18 6777 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:06:05 5370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:06:02 7781 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:05:24 7295 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:04:54 6781 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:04:28 7295 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:03:37 7781 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:03:22 7780 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:03:17 570 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 04:03:11 6777 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:02:20 6287 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:00:42 6772 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:00:35 6283 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:00:24 7770 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 04:00:04 7774 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:59:41 6771 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:58:56 3772 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:58:56 3773 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:58:55 3775 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:58:08 3777 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:58:08 3779 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:58:07 3777 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:58:05 560 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:58:05 7288 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:57:14 6284 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:57:14 7289 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:56:15 6289 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:55:46 6774 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:55:16 5760 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:54:47 3770 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:54:47 3772 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:54:46 3773 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:53:46 3770 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:53:46 3772 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:53:45 3771 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:53:03 6282 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:52:45 6772 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:51:58 7768 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:51:12 6767 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:50:31 6277 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:50:28 3769 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:50:28 3770 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:50:27 3771 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:50:09 3773 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:50:09 3774 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:50:08 3773 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:50:04 5760 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:49:45 6764 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:49:25 7762 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:48:55 6266 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:48:35 7270 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:48:16 7272 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:48:10 6758 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:47:16 950 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:46:10 6759 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:45:55 6758 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:45:12 6267 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:44:46 7754 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:44:30 7754 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:44:10 6262 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:43:51 6266 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:43:28 3756 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:43:28 3758 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:43:27 3760 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:43:10 7269 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:42:20 7262 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:42:15 3752 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:42:15 3753 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:42:14 3752 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:42:09 7751 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:42:04 950 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:41:54 7753 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:40:32 6258 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:40:14 6257 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:39:59 7259 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:39:15 6130 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:38:45 7259 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:37:21 3751 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:37:21 3753 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:37:20 3753 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:36:28 7266 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:35:19 3757 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:35:19 3759 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:35:18 3753 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:35:00 6259 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:34:45 6259 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:34:34 7263 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:34:14 6747 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:34:03 6150 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:33:38 3747 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:33:38 3749 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:33:37 3750 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:31:15 1340 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:30:55 7746 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:30:30 3747 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:30:30 3748 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:30:29 3747 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:29:36 7746 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:29:31 6744 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:29:19 7260 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:28:54 3741 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:28:54 3743 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:28:53 3743 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:28:11 7739 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:27:18 6247 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:26:52 3739 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:26:52 3741 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:26:51 3739 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:26:03 1340 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:25:59 7246 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:24:46 6729 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:24:31 7733 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:24:30 6242 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:23:56 7242 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:23:14 6540 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:22:50 7242 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:22:25 6730 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:22:22 6241 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:21:41 7731 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:19:52 6237 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:19:18 7727 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:18:57 6725 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:18:02 6530 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:17:56 6721 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:16:48 6721 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:16:29 6721 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:16:23 7722 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:15:50 7719 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:15:34 7228 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:15:14 1730 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:14:05 7229 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:13:46 3714 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:13:46 3716 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:13:45 3717 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:13:23 7713 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:12:53 3712 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:12:53 3713 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:12:52 3712 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:11:49 7225 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:10:49 6710 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:10:02 1720 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:09:53 3713 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:09:53 3715 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:09:52 3716 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:09:32 6714 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:09:25 7718 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:08:40 3713 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:08:40 3715 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:08:39 3715 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:08:15 7224 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:08:04 6708 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:07:13 6920 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:06:59 3711 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:06:59 3712 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:06:58 3713 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:06:29 6707 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:05:58 3713 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:05:58 3714 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:05:57 3712 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:05:03 6216 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:04:44 6704 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:04:22 6703 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:03:37 6701 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:02:07 9320 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 03:02:02 6699 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:01:57 7215 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:01:37 7214 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:01:30 6209 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:01:20 3699 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:01:20 3701 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 03:01:19 3703 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:01:05 3703 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 03:01:05 3704 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 03:01:04 3705 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:00:26 7702 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 03:00:05 7702 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:59:57 3700 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:59:57 3701 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:59:56 3702 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:59:19 4520 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:59:01 6208 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:57:39 3701 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:57:39 3703 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:57:38 3702 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:56:28 6212 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:56:28 6700 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:56:01 7213 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:54:07 4520 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:53:11 6696 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:52:56 7697 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:51:18 9720 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:50:50 6201 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:50:35 6202 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:50:30 6692 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:50:04 3693 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:50:04 3694 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:50:03 3696 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:48:09 3692 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:48:09 3693 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:48:08 3692 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:47:29 6687 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:46:58 7689 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:46:06 9710 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:45:49 6196 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:45:13 7199 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:45:05 3685 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:45:05 3687 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:45:04 3687 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:43:41 6195 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:43:18 4910 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:42:41 3682 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:42:41 3684 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:42:40 3684 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:42:14 7679 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:41:55 7679 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:40:29 7189 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:38:20 7184 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:38:06 4900 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:37:01 6183 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:36:46 6673 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:36:30 7675 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:35:18 90 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:34:25 6180 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:33:41 6670 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:33:26 7671 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:33:21 3670 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:33:21 3672 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:33:20 3673 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:33:05 2182 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 02:33:00 2183 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 02:32:32 6176 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:32:16 7178 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:32:01 6662 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:31:46 6661 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:31:42 7663 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:30:49 6171 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:30:06 100 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:30:01 3664 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:30:01 3666 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:30:00 3665 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:28:09 7658 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:27:43 6167 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:27:17 5290 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:26:19 6167 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:26:13 7174 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:26:13 7658 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:25:49 3656 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:25:49 3658 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:25:48 3659 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:25:08 3658 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:25:08 3659 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:25:07 3660 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:24:22 7652 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:23:20 7649 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:22:11 3646 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:22:11 3648 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:22:10 3649 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:22:05 5290 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:21:29 3648 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:21:29 3649 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:21:28 3648 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:21:20 7646 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:21:08 6645 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:19:56 6643 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:19:52 7644 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:19:17 490 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 02:18:47 7646 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:18:39 3644 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:18:39 3645 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 02:18:38 3647 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:18:20 3644 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 02:18:20 3645 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 02:18:19 3645 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:18:09 6640 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:17:26 6641 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:17:17 7643 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:17:02 7643 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 02:16:58 7154 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error