Event List (682596)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Unit DeltaV 2016-05-15 14:08:31 8481 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:07:45 7990 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:07:31 190 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 14:07:03 7987 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:06:44 7473 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:06:22 8474 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:05:48 7478 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:05:09 8473 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:04:46 8470 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:04:44 4470 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 14:04:44 4471 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 14:04:43 4473 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:04:03 4469 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 14:04:03 4470 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 14:04:02 4469 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:02:47 6977 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:02:31 8467 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 14:02:25 2590 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 14:00:38 8466 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:59:57 6972 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:59:54 4461 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:59:54 4463 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:59:53 4465 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:59:36 7780 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:59:14 4466 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:59:14 4467 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:59:13 4466 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:58:49 6973 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:58:35 8464 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:58:20 8464 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:57:29 6971 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:57:25 7461 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:54:58 7974 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:54:46 7457 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:54:24 7780 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:53:49 8457 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:53:16 8459 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:53:13 4459 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:53:13 4461 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:53:12 4462 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:51:36 2980 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:51:23 7965 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:51:03 4455 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:51:03 4457 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:51:02 4455 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:50:51 6960 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:50:12 4448 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:50:12 4449 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:50:11 4451 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:49:35 4449 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:49:35 4451 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:49:34 4449 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:49:05 7448 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:48:50 7449 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:48:31 6959 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:46:24 2970 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:46:24 6956 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:46:09 6956 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:44:43 6947 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:44:27 7948 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:43:35 8170 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:43:10 6951 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:42:20 7944 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:39:49 8440 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:39:28 7951 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:38:32 8433 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:38:23 8170 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:37:42 7947 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:37:32 8435 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:37:17 6944 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:37:02 6944 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:36:12 7951 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:35:35 3370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:35:29 6942 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:34:45 7948 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:34:45 8436 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:33:57 6944 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:33:30 7431 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:32:28 6940 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:32:28 7428 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:30:39 6937 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:30:37 4427 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:30:37 4429 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:30:36 4430 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:30:23 3360 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:30:19 4427 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:30:19 4428 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:30:18 4427 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:29:35 7939 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:29:13 7937 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:29:01 7421 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:28:46 7422 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:27:34 8560 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:24:55 7935 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:24:32 7417 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:23:52 7415 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:23:45 7933 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:23:06 7930 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:22:52 4419 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:22:52 4420 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:22:51 4420 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:22:22 8550 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:22:05 4418 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:22:05 4419 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:22:04 4418 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:21:01 7931 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:20:14 6924 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:19:53 7412 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:19:34 3750 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:19:31 7411 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:18:16 6917 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:16:32 2929 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 13:16:28 2929 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 13:16:23 7413 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:16:08 7411 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:15:54 8415 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:14:22 3750 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:13:47 8414 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:13:15 4414 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:13:15 4416 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:13:14 4416 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:12:26 7408 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:12:04 8409 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:11:41 7919 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:11:33 8950 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:11:24 7406 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:11:04 7919 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:07:11 4402 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:07:11 4404 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:07:10 4401 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:06:21 8940 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:05:50 8396 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:05:06 6904 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:04:42 6905 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:04:34 4394 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:04:34 4396 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 13:04:33 4398 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:03:35 7907 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:03:33 4140 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 13:02:29 4389 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 13:02:29 4390 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 13:02:28 4390 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:02:02 6897 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:01:03 7383 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 13:00:45 8387 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:59:54 4384 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:59:54 4386 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:59:53 4386 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:59:00 8385 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:58:21 4140 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:57:45 7897 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:55:32 9330 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:55:26 7385 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:55:17 4389 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:55:17 4390 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:55:16 4388 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:55:14 6895 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:54:38 4386 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:54:38 4388 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:54:37 4389 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:54:20 4389 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:54:20 4390 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:54:19 4389 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:53:44 4384 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:53:44 4386 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:53:43 4387 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:53:28 6894 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:53:12 4388 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:53:12 4389 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:53:11 4387 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:52:53 7897 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:51:52 6893 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:50:20 9330 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:49:40 6886 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:49:21 7889 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:48:07 7888 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:47:49 6882 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:47:33 7372 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:47:32 4530 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:46:40 8371 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:45:57 7368 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:45:26 7884 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:44:40 8371 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:43:23 7368 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:43:08 8369 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:42:31 8368 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:42:26 7363 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:42:22 4364 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:42:22 4366 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:42:21 4368 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:42:20 4520 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:42:05 4367 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:42:05 4368 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:42:04 4367 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:41:21 7878 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:40:16 6872 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:39:31 9720 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:39:22 4361 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:39:22 4363 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:39:21 4364 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:38:10 4363 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:38:10 4364 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:38:09 4364 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:37:00 6875 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:36:54 7362 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:36:54 7877 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:36:35 4364 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:36:35 4366 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:36:34 4367 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:35:10 6872 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:34:37 8364 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:34:19 9720 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:34:17 4363 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:34:17 4364 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:34:16 4365 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:34:03 7873 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:33:00 2873 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 12:32:56 2873 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 12:32:29 8361 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:31:31 4920 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:31:19 7355 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:31:11 7870 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:31:01 6866 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:30:38 4356 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:30:38 4358 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:30:37 4358 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:30:00 7354 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:29:04 4355 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:29:04 4356 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:29:03 4356 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:28:44 7350 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:28:38 7864 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:28:14 8351 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:27:27 8349 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:27:25 4349 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:27:25 4351 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:27:24 4352 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:26:43 4349 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:26:43 4351 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:26:42 4349 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:26:19 4910 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:26:01 7340 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:25:44 7339 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:25:08 6852 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:24:47 8343 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:24:33 4342 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:24:33 4344 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:24:32 4344 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:23:31 110 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:23:26 4343 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:23:26 4344 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:23:25 4344 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:22:21 6852 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:22:08 7853 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:20:50 7851 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:20:22 7852 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:20:18 7336 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:18:57 7333 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:18:19 100 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:18:01 8336 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:17:29 4333 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:17:29 4334 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:17:28 4336 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:17:13 4337 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:17:13 4338 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:17:12 4337 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:16:58 7846 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:16:43 7333 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:15:54 7334 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:15:30 5300 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:14:43 7848 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:14:41 4334 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:14:41 4336 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:14:40 4337 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:13:25 4334 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:13:25 4335 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:13:24 4334 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:12:08 7328 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:11:22 7326 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:11:18 8326 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:10:38 8328 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:10:18 5300 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:10:13 4327 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:10:13 4328 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 12:10:12 4329 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:09:41 6835 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:08:21 8324 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:07:30 500 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:06:48 7323 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:05:45 2837 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 12:05:40 2837 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 12:05:36 7836 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:05:06 8322 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:04:56 7834 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:04:17 7320 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:03:55 4322 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 12:03:55 4321 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 12:03:54 4323 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:03:26 6828 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:02:30 7832 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:02:18 490 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 12:02:14 7315 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:01:34 7311 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:01:27 7826 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:01:09 7312 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 12:00:45 7825 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:59:59 7310 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:59:45 7822 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:59:42 6818 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:59:29 5690 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:59:11 6819 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:58:52 7305 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:58:09 7822 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:57:46 8308 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:57:32 4307 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:57:32 4309 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:57:31 4309 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:56:46 8310 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:56:18 7309 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:55:53 4314 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:55:53 4315 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:55:52 4314 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:55:20 6821 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:55:20 7822 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:54:30 8308 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:54:17 5690 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:54:14 8308 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:53:31 6815 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:53:07 4304 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:53:07 4306 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:53:06 4307 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:52:15 7819 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:51:29 890 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:51:13 4307 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:51:13 4308 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:51:12 4307 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:50:50 7814 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:50:16 8299 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:50:00 4296 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:50:00 4298 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:49:59 4300 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:49:41 4303 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:49:41 4304 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:49:40 4303 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:49:17 8302 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:48:35 2816 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 11:48:32 2814 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 11:48:03 6810 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:47:48 7297 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:46:31 6808 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:46:17 880 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:45:13 7294 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:44:07 4294 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:44:07 4296 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:44:06 4298 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:43:36 4296 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:43:36 4297 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:43:35 4295 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:43:28 6080 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:42:56 7805 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:42:39 7805 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:40:15 7796 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:39:58 7791 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:38:57 8273 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:38:16 6070 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:38:07 7279 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:37:46 8282 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:37:43 4282 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:37:43 4284 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:37:42 4285 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:37:10 4281 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:37:10 4282 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:37:09 4282 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:36:29 6789 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:35:58 7794 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:35:28 1270 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:35:17 6791 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:34:59 7283 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:34:56 4284 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:34:56 4286 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:34:55 4287 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:34:03 7794 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:33:34 4283 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:33:34 4284 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:33:33 4284 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:33:23 8283 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:32:00 8279 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:31:54 7276 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:30:50 7275 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:30:48 4278 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:30:48 4279 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:30:47 4281 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:30:30 4281 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:30:30 4282 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:30:29 4280 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:30:16 1270 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:29:29 6787 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:28:45 7788 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:28:10 7786 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:27:55 8274 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:27:37 6784 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:27:27 6470 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:26:50 8271 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:26:06 7270 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:26:00 2786 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 11:25:55 2784 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2016-05-15 11:25:38 8272 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:25:00 6781 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:24:39 7268 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:24:03 8269 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:22:35 4266 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:22:35 4268 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:22:34 4269 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:22:15 6460 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:22:15 8267 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:21:52 8266 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:21:08 7263 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:20:46 4264 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:20:46 4266 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:20:45 4265 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:20:19 6772 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:20:01 7262 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:19:52 7776 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:19:41 4262 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:19:41 4263 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:19:40 4264 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:19:27 1660 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:18:46 4265 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:18:46 4267 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:18:45 4265 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:15:17 7770 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:15:13 8258 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:14:15 1650 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:13:40 4258 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:13:40 4260 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:13:39 4261 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:13:38 8259 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:12:58 4259 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:12:58 4260 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:12:57 4259 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:12:22 7774 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:11:39 4252 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:11:39 4254 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 11:11:38 4255 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:11:26 6860 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:10:07 4255 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 11:10:07 4256 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 11:10:06 4255 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:08:33 8249 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:07:42 6755 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:06:43 6760 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:06:14 6850 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:04:53 8244 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:03:26 2050 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 11:01:52 7754 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:00:29 8234 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 11:00:12 7232 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:58:49 8232 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:58:14 2040 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 10:58:09 7744 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:57:47 6739 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:57:05 4229 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:57:05 4230 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 10:57:04 4231 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:56:26 7742 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:55:25 7240 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 10:54:40 6736 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:52:49 4232 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:52:49 4234 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 10:52:48 4232 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:51:06 4228 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:51:06 4229 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 10:51:05 4230 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:51:04 7226 ALARM INSTRUMENT BOILER CNTR01 TI101 PR Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:50:49 4230 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:50:49 4231 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 10:50:48 4231 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:50:14 6736 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:50:13 7240 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 10:49:26 6736 ALARM INSTRUMENT BOILER CNTR01 PR9116_1 POT 1 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:49:10 4225 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:49:10 4227 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 10:49:09 4228 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:48:48 4227 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:48:48 4228 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 10:48:47 4226 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:47:46 7736 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:47:25 2440 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 10:46:02 4219 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:46:02 4221 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active
SHP Unit DeltaV 2016-05-15 10:46:01 4222 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:45:04 4219 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:45:04 4220 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2016-05-15 10:45:03 4219 ALARM INSTRUMENT BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:44:55 7729 ALARM INSTRUMENT BOILER CNTR01 PR9116_2 POT 2 DEV_OFFLINE_ALM INACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:42:19 4830 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 10:41:50 8214 ALARM INSTRUMENT BOILER CNTR01 PR9202_1 HiHi Switch DEV_OFFLINE_ALM ACT/UNACK 15-CRITICAL COMM Communication Error
SHP Unit DeltaV 2016-05-15 10:39:31 30 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2016-05-15 10:39:24 4213 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 I/O Input Failure
SHP Unit DeltaV 2016-05-15 10:39:24 4214 EVENT PROCESS BOILER CNTR01 PR_CAB_TEMP PR9106 Cabinet Temperature ACTIVE 4-INFO PR_CAB_TEMP/AI1 Module Failure Active