Event List (683188)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Unit DeltaV 2018-03-27 09:14:19 7874 EVENT PROCESS BOILER CNTR01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:14:19 7911 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2018-03-27 09:14:19 7913 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:14:19 7914 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO Error Cleared Outputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:14:19 7915 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Unit DeltaV 2018-03-27 09:14:19 8338 EVENT PROCESS BOILER CNTR01 AI200 Workshop General Analogue in ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:14:19 8362 EVENT PROCESS BOILER CNTR01 TI905 Phoenix Contact TC 01 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Unit DeltaV 2018-03-27 09:14:19 8363 EVENT PROCESS BOILER CNTR01 TI905 Phoenix Contact TC 01 ACTIVE 4-INFO Error Cleared Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:14:19 8364 ALARM INSTRUMENT BOILER CNTR01 TI905 Phoenix Contact TC 01 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2018-03-27 09:14:03 8240 STATUS SYSTEM AREA_A PROPLUS CNTR01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Unit DeltaV 2018-03-27 09:13:53 836 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT IO: No Communications On Port - Serial Card, C01, P01
SHP Unit DeltaV 2018-03-27 09:13:53 2369 ALARM INSTRUMENT BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1327 EVENT PROCESS BOILER CNTR01 S7_RIO_01 Siemens ET200S Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1334 EVENT PROCESS BOILER CNTR01 S7_RIO_01 Siemens ET200S Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1339 EVENT PROCESS BOILER CNTR01 S7_RIO_01 Siemens ET200S Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_01/OWNSTATE Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1346 EVENT PROCESS BOILER CNTR01 S7_RIO_01 Siemens ET200S Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_01/COMP_STATE_01 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1353 EVENT PROCESS BOILER CNTR01 S7_RIO_01 Siemens ET200S Remote IO Via Red Lion EVENT_LIMITED. 4-INFO S7_RIO_01/COMP_STATE_02 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1826 EVENT PROCESS BOILER CNTR01 S7_RIO_02 Siemens ET200SP Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_02/RL_DEV_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1836 EVENT PROCESS BOILER CNTR01 S7_RIO_02 Siemens ET200SP Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_02/RL_DEV_ONLINE Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1844 EVENT PROCESS BOILER CNTR01 S7_RIO_02 Siemens ET200SP Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_02/OWNSTATE Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1851 EVENT PROCESS BOILER CNTR01 S7_RIO_02 Siemens ET200SP Remote IO Via Red Lion ACTIVE 4-INFO S7_RIO_02/COMP_STATE_01 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 1859 EVENT PROCESS BOILER CNTR01 S7_RIO_02 Siemens ET200SP Remote IO Via Red Lion EVENT_LIMITED. 4-INFO S7_RIO_02/COMP_STATE_02 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2348 EVENT PROCESS BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2359 EVENT PROCESS BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/RL_DEV_ONLINE Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2367 EVENT PROCESS BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2374 EVENT PROCESS BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO ACTIVE 4-INFO BUS_COUPLER_01/STATUS_REG_7997 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2381 EVENT PROCESS BOILER CNTR01 BUS_COUPLER_01 Phoenix Contact Remote IO EVENT_LIMITED. 4-INFO BUS_COUPLER_01/STATUS_REG_7996 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2829 EVENT PROCESS BOILER CNTR01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_0 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2837 EVENT PROCESS BOILER CNTR01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/DIGITAL_IN_1 Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2856 EVENT PROCESS BOILER CNTR01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI2/REGISTER_0_IN Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2864 EVENT PROCESS BOILER CNTR01 CNTR01_HOLD Controller 01 holding Module ACTIVE 4-INFO CNTR01_HOLD/BC01_AI2/REGISTER_1_IN Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 2875 EVENT PROCESS BOILER CNTR01 CNTR01_HOLD Controller 01 holding Module EVENT_LIMITED. 4-INFO CNTR01_HOLD/S7PL_WATCHDOG_IN Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 3327 EVENT PROCESS BOILER CNTR01 AI200 Workshop General Analogue in ACTIVE 4-INFO AI200/RAW_INPUT Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 3827 EVENT PROCESS BOILER CNTR01 PR9202_1 HiHi Switch ACTIVE 4-INFO PR9202_1/ERROR_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 3834 EVENT PROCESS BOILER CNTR01 PR9202_1 HiHi Switch ACTIVE 4-INFO PR9202_1/ERROR_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 3840 EVENT PROCESS BOILER CNTR01 PR9202_1 HiHi Switch ACTIVE 4-INFO PR9202_1/MEASURE_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 3853 EVENT PROCESS BOILER CNTR01 PR9202_1 HiHi Switch ACTIVE 4-INFO PR9202_1/RL_DEVICE_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 3863 EVENT PROCESS BOILER CNTR01 PR9202_1 HiHi Switch EVENT_LIMITED. 4-INFO PR9202_1/RL_DEVICE_ONLINE Outputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7348 EVENT PROCESS BOILER CNTR01 TI101 Unit External Temperature ACTIVE 4-INFO TI101/MEASURE_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7353 EVENT PROCESS BOILER CNTR01 TI101 Unit External Temperature ACTIVE 4-INFO TI101/ERROR_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7356 EVENT PROCESS BOILER CNTR01 TI101 Unit External Temperature ACTIVE 4-INFO TI101/ERROR_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7360 EVENT PROCESS BOILER CNTR01 TI101 Unit External Temperature ACTIVE 4-INFO TI101/MODBUS_IN Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7367 EVENT PROCESS BOILER CNTR01 TI101 Unit External Temperature EVENT_LIMITED. 4-INFO TI101/AI1 I/O Input Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7879 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO TI102/MEASURE_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7883 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO TI102/ERROR_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7887 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO TI102/ERROR_STATUS Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7894 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature ACTIVE 4-INFO TI102/MODBUS_IN Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 7900 EVENT PROCESS BOILER CNTR01 TI102 Server Cabinet temperature EVENT_LIMITED. 4-INFO TI102/AI1 I/O Input Failure
SHP Unit DeltaV 2018-03-27 09:13:52 8344 EVENT PROCESS BOILER CNTR01 TI905 Phoenix Contact TC 01 ACTIVE 4-INFO TI905/REGISTER_IN Inputs Transfer Failure
SHP Unit DeltaV 2018-03-27 09:13:52 8356 EVENT PROCESS BOILER CNTR01 TI905 Phoenix Contact TC 01 ACTIVE 4-INFO TI905/AI1/ALM1 I/O Input Failure
SHP Unit DeltaV 2018-03-27 09:13:52 8363 ALARM INSTRUMENT BOILER CNTR01 TI905 Phoenix Contact TC 01 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2018-03-25 10:46:56 7130 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Unit DeltaV 2018-03-25 10:46:50 4730 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Unit DeltaV 2018-03-23 12:31:46 1200 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - AS01
SHP Unit DeltaV 2018-03-23 12:31:26 1190 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - AS01
SHP Office DeltaV 2018-03-21 15:57:57 9470 CHANGE USER AREA_A PROPLUS LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:57:54 7180 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:57:52 3000 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:45:10 4770 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT IO: Not Communicating - DI Card, C06
SHP Office DeltaV 2018-03-21 15:45:06 4769 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT IO: Not Communicating - DI Card, C06
SHP Office DeltaV 2018-03-21 15:33:03 800 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:26:47 410 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:26:08 8060 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:25:49 5090 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:25:45 8890 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:25:03 7540 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:25:03 7850 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:24:40 4000 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:24:14 3170 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:23:27 7510 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:23:03 2440 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:23:03 4160 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:23:00 6390 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:23:00 7170 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:23:00 7950 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:22:06 4440 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:19:51 6282 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PID1/GAIN.CV ADMINISTRATOR NEW VALUE = 1.4
SHP Office DeltaV 2018-03-21 15:19:27 3760 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 15:19:27 4860 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 15:19:06 910 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 15:18:53 9390 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 15:18:51 6450 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 15:18:44 3025 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2018-03-21 15:18:44 3026 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2018-03-21 15:18:44 3027 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 15:18:43 3031 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 I/O Input Failure
SHP Office DeltaV 2018-03-21 15:18:43 3032 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 Module Failure Active
SHP Office DeltaV 2018-03-21 15:18:43 3034 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 8
SHP Office DeltaV 2018-03-21 15:18:43 3036 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 4
SHP Office DeltaV 2018-03-21 15:18:43 3038 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2018-03-21 15:18:43 3039 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2018-03-21 15:18:43 3041 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2018-03-21 15:18:43 3042 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2018-03-21 15:18:43 3044 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 15:18:42 2570 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 15:18:42 2641 DOWNLOAD USER BOILER CNTRL01 PIC101 Steam Pressure UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 15:18:42 2715 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 15:18:42 5960 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 15:18:42 9540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 15:18:41 9702 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 15:16:26 570 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:16:26 2600 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:10:29 230 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 15:10:27 2320 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 15:10:27 3220 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 15:10:27 4020 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 15:10:27 5720 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 15:09:00 9050 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 15:08:59 800 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 15:08:59 2040 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 15:08:59 3290 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 15:08:59 5160 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 15:06:04 5940 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 15:06:03 960 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 15:06:02 6600 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 15:06:02 7840 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 15:06:02 9090 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 15:04:35 9840 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 15:04:23 9100 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 15:04:21 5540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 15:04:18 6210 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:04:13 2065 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2018-03-21 15:04:12 180 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2018-03-21 15:04:12 895 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 15:04:12 965 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 15:04:12 1045 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 15:04:12 2083 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/DI1 I/O Input Failure
SHP Office DeltaV 2018-03-21 15:04:12 4334 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 15:04:12 8030 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 15:04:11 8129 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 15:04:05 1310 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:02:27 3830 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 15:02:14 9030 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 14:51:51 9180 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:51:37 4720 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:51:33 5570 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:51:22 1690 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:51:21 1821 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:51:21 3007 DOWNLOAD USER AREA_A CNTRL01 IO1/C06 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:51:21 3315 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:51:21 3382 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:51:21 5958 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:51:20 7180 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:51:20 8110 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:49:59 440 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2018-03-21 14:49:30 7770 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:49:19 2640 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:49:17 4240 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:49:08 1393 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:49:08 2660 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:49:08 3017 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT IO: Not Communicating - DI Card, C06
SHP Office DeltaV 2018-03-21 14:49:07 160 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold start memory download is preempted
SHP Office DeltaV 2018-03-21 14:49:07 460 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 1-DISABLED Cold start memory download is preempted
SHP Office DeltaV 2018-03-21 14:49:07 2835 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:49:07 3821 DOWNLOAD USER AREA_A CNTRL01 IO1/C01 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 4644 DOWNLOAD USER AREA_A CNTRL01 CNTRL01C01CH01 UPDATE Administrator Download Device Alarm
SHP Office DeltaV 2018-03-21 14:49:07 4657 DOWNLOAD USER AREA_A CNTRL01 IO1/C02 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 4759 DOWNLOAD USER AREA_A CNTRL01 IO1/C03 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 4993 DOWNLOAD USER AREA_A CNTRL01 IO1/C04 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 5240 DOWNLOAD USER AREA_A CNTRL01 IO1/C05 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 5359 DOWNLOAD USER AREA_A CNTRL01 IO1/C07 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 6783 DOWNLOAD USER AREA_A CNTRL01 IO1/C08 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 14:49:07 7258 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:49:07 7354 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:49:01 4140 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:48:59 4330 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:48:59 6388 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:48:58 4858 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:48:58 4927 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:48:56 4426 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:48:56 5704 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 14:48:56 5909 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 14:48:40 8140 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:48:39 670 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 14:48:39 1920 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 14:48:39 3790 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 14:48:38 9420 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:48:28 8630 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2018-03-21 14:48:15 4310 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:48:10 2951 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT IO: Not Communicating - DI Card, C06
SHP Office DeltaV 2018-03-21 14:48:00 9750 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:47:54 2510 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:47:43 1590 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:47:42 1703 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:47:42 3993 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:47:42 4043 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 14:47:42 4093 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:47:42 6855 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:38:55 3630 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:38:42 9450 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:38:40 9020 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:38:31 619 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:38:31 674 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 14:38:31 768 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:38:31 3487 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:38:31 8540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:38:30 8699 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:37:11 5510 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 14:26:48 2830 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:26:36 5980 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:26:33 8220 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:26:25 329 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:26:25 4910 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:26:24 5111 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:26:24 7466 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:26:24 7521 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 14:26:24 7602 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:26:04 3940 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 14:25:49 5546 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN2.CV ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2018-03-21 14:22:00 1920 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:21:49 4900 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:21:46 7450 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:21:38 3670 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:21:37 3770 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:21:37 6072 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:21:37 6128 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 14:21:37 6214 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:21:37 8995 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:21:13 1540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:20:58 4280 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2018-03-21 14:20:58 8396 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN2.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 14:20:56 3840 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:20:56 5560 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2018-03-21 14:20:54 7150 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:20:45 2610 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:20:44 2743 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:20:44 4910 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 14:20:44 4980 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:20:44 4994 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:20:44 7776 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:19:49 1290 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:19:42 56 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN2.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 14:19:36 8830 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 14:19:34 6830 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:19:25 46 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 14:19:25 136 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 14:19:25 2929 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 14:19:25 7600 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 14:19:24 7807 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 14:19:24 9995 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 14:18:50 1120 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 14:14:57 2990 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level PID1/HI_HI_LIM.CV ADMINISTRATOR NEW VALUE = 850
SHP Office DeltaV 2018-03-21 14:14:34 9995 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = AUTO
SHP Office DeltaV 2018-03-21 14:04:35 6420 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 14:04:22 860 CHANGE USER AREA_A PROPLUS LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 14:04:21 8680 CHANGE USER AREA_A PROPLUS LOGOFF <none>
SHP Office DeltaV 2018-03-21 14:03:31 9690 CHANGE USER AREA_A PROPLUS LOGOFF OPERATOR
SHP Office DeltaV 2018-03-21 14:02:40 550 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF OPERATOR
SHP Office DeltaV 2018-03-21 14:01:12 3350 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF OPERATOR
SHP Office DeltaV 2018-03-21 14:00:54 830 CHANGE USER AREA_A PROPLUS REMOTE LOGON OPERATOR
SHP Office DeltaV 2018-03-21 14:00:29 2940 CHANGE USER AREA_A PROPLUS REMOTE LOGON OPERATOR
SHP Office DeltaV 2018-03-21 14:00:19 5803 CHANGE USER BOILER PROPLUS F106 Combustion Air Fan DC1/SP_D.CV OPERATOR NEW VALUE = STOP
SHP Office DeltaV 2018-03-21 13:58:04 7170 CHANGE USER AREA_A PROPLUS LOGOFF <none>
SHP Office DeltaV 2018-03-21 13:58:04 8730 CHANGE USER AREA_A PROPLUS LOGON OPERATOR
SHP Office DeltaV 2018-03-21 13:56:52 9700 CHANGE USER AREA_A PROPLUS LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:56:36 9170 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:52:18 9400 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:50:28 6418 CHANGE USER BOILER PROPLUS DEMO1 Control Module SWITCH.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:50:11 190 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:49:59 7434 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN1.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:49:58 6950 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:49:56 5740 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:49:47 960 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 13:49:47 5730 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:49:46 5851 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:49:46 8115 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 13:49:46 8170 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 13:49:46 8223 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:47:54 5833 CHANGE USER BOILER PROPLUS DEMO1 Control Module SWITCH.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:47:35 9830 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:47:28 153 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN1.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:47:24 4080 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:47:21 5370 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:47:13 2690 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:47:12 2767 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:47:12 4924 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 13:47:12 4981 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 13:47:12 5058 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:47:12 7784 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 13:46:21 4952 CHANGE USER BOILER PROPLUS DEMO1 Control Module SWITCH.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:44:36 552 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN2.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:44:36 9280 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:44:24 5260 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:44:22 4660 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:44:13 910 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:44:12 964 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:44:12 3298 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 13:44:12 3364 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 13:44:12 3415 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:44:12 6197 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 13:41:34 5925 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN1.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 13:41:14 9000 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:41:01 4370 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:40:53 3250 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:40:41 1765 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 13:40:41 1802 DOWNLOAD USER BOILER CNTRL01 DEMO1 UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 13:40:41 1853 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:40:41 2510 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:40:41 3130 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 13:40:41 4380 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:40:41 4597 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 13:40:41 9370 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:40:40 9458 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:40:15 4150 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:40:00 6580 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:37:55 7790 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:37:43 4870 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 13:37:41 3810 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:37:32 4110 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 13:37:32 8299 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2018-03-21 13:37:31 4153 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:37:31 6070 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2018-03-21 13:37:31 6659 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 13:37:31 6715 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 13:37:31 6819 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:37:31 7400 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 13:37:31 8020 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 13:37:31 8309 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/DI1 I/O Input Failure
SHP Office DeltaV 2018-03-21 13:37:31 9270 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 13:37:31 9903 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 13:32:59 4300 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:32:56 9810 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 13:32:45 4990 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 12:32:29 8635 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2018-03-21 12:32:29 9140 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2018-03-21 12:32:28 8540 CHANGE USER AREA_A PROPLUS PROPLUS MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2018-03-21 12:32:28 8563 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2018-03-21 12:31:50 4707 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 327.602 Limit 300
SHP Office DeltaV 2018-03-21 12:31:34 4697 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/ACK 11-WARNING LOW Low Alarm Value 226.558 Limit 300
SHP Office DeltaV 2018-03-21 12:31:34 4700 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 12:31:33 4713 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 12:31:33 4729 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2018-03-21 12:30:55 4678 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 239.028 Limit 300
SHP Office DeltaV 2018-03-21 12:30:43 3141 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2018-03-21 12:30:43 3159 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2018-03-21 12:30:43 5668 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 12:22:36 3340 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:22:26 7400 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2018-03-21 12:22:21 8570 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2018-03-21 12:22:20 2350 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:22:20 9830 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2018-03-21 12:22:19 9850 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2018-03-21 12:22:18 1290 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:22:09 1740 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:22:09 8309 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM INACT/ACK 07-ADVISORY OK IO: Channel Error - AI Card, C01, CH05
SHP Office DeltaV 2018-03-21 12:22:08 1852 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:22:08 3169 DOWNLOAD USER AREA_A CNTRL01 IO1/C01 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 12:22:08 4186 DOWNLOAD USER AREA_A CNTRL01 CNTRL01C01CH01 UPDATE Administrator Download Device Alarm
SHP Office DeltaV 2018-03-21 12:22:08 4239 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:22:08 4299 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 12:22:08 7305 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 12:21:07 4940 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:20:56 6050 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2018-03-21 12:20:55 6380 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:20:53 640 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:20:44 1262 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 12:20:44 5620 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:20:43 5810 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:20:43 7077 DOWNLOAD USER AREA_A CNTRL01 IO1/C01 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2018-03-21 12:20:43 8184 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 12:20:43 8235 DOWNLOAD USER AREA_A CNTRL01 CNTRL01C01CH01 UPDATE Administrator Download Device Alarm
SHP Office DeltaV 2018-03-21 12:20:43 8287 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:20:43 8309 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE IO: Channel Error - AI Card, C01, CH05
SHP Office DeltaV 2018-03-21 12:18:30 4250 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:18:27 5540 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:18:27 7100 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:18:25 1270 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:18:16 480 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:18:14 980 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:18:14 2389 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 12:18:13 1054 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 12:18:13 1133 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:18:11 536 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:18:11 1729 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 12:18:11 1943 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 12:18:10 6810 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:18:09 120 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 12:18:09 1990 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 12:18:08 7620 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:18:08 8870 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 12:08:40 1540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:08:36 670 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:08:26 7530 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:08:24 7570 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:08:24 9405 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 12:08:23 8263 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 12:08:23 8318 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:08:21 7712 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:08:21 8957 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 12:08:21 9159 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 12:07:45 9190 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - GEM1
SHP Office DeltaV 2018-03-21 12:07:42 1440 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:07:37 5260 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 12:07:28 1660 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:07:26 2630 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 12:07:26 3676 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 12:07:25 2701 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 12:07:25 2783 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:07:25 3430 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:07:25 4050 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 12:07:25 5300 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 12:07:23 2182 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:07:23 3394 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 12:07:23 3602 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2018-03-21 12:07:22 6280 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 12:07:22 6910 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2018-03-21 12:07:22 8470 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 11:54:57 2530 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 11:51:17 4120 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2018-03-21 11:50:21 2670 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2018-03-21 11:41:04 6740 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:40:50 2590 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:40:49 740 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:40:38 600 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:40:15 3754 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/OUT.CV ADMINISTRATOR NEW VALUE = 39.59
SHP Office DeltaV 2018-03-21 11:40:12 5024 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2018-03-21 11:36:52 570 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2018-03-21 11:36:52 570 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2018-03-21 11:36:37 340 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2018-03-21 11:36:35 5876 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2018-03-21 11:36:35 9110 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2018-03-21 11:35:18 670 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NOT COMMUNICATING 4-INFO Previous node status was: OK
SHP Office DeltaV 2018-03-21 11:35:03 440 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2018-03-21 11:34:51 6778 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2018-03-21 11:34:49 9240 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2018-03-21 11:34:47 9430 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2018-03-21 11:34:46 710 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2018-03-21 11:34:43 6965 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Device Connection Failure - PROPLUS
SHP Office DeltaV 2018-03-21 11:32:43 6110 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:32:32 5190 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:32:30 2100 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:32:21 1940 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:32:20 2040 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 11:32:20 5098 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Module Delete
SHP Office DeltaV 2018-03-21 11:32:20 5306 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 11:32:20 5358 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 11:32:20 9531 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 11:31:53 6440 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:31:42 4120 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:31:40 1810 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:31:31 3200 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:31:30 3336 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 11:31:30 5592 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 11:31:30 5618 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2018-03-21 11:31:30 5686 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 11:31:30 6340 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 11:31:30 6960 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2018-03-21 11:31:30 8210 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 11:31:30 8312 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 11:31:02 5560 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:30:50 9490 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:30:48 1570 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:30:39 2149 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Module Delete
SHP Office DeltaV 2018-03-21 11:30:39 2365 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2018-03-21 11:30:39 2420 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 11:30:39 6584 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 11:30:39 8890 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:30:38 8988 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2018-03-21 11:24:01 5620 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:23:49 4880 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:23:47 1010 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:23:38 4430 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:13:57 1220 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2018-03-21 11:13:57 5120 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:13:46 7950 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:13:45 6052 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Standby Unavailable
SHP Office DeltaV 2018-03-21 11:13:44 490 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:13:42 990 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NO CONFIGURATION
SHP Office DeltaV 2018-03-21 11:13:38 8230 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2018-03-21 11:13:38 9633 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2018-03-21 11:13:36 2143 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2018-03-21 11:13:35 2147 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2018-03-21 11:13:35 2149 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2018-03-21 11:13:35 2150 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 568.193 Limit 300
SHP Office DeltaV 2018-03-21 11:13:35 2152 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 11:13:35 2652 EVENT PROCESS BOILER CNTRL01 TIC102 Boiler temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2018-03-21 11:13:35 3141 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2018-03-21 11:13:35 3142 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2018-03-21 11:13:35 3144 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 11:13:35 4690 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:13:35 6052 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Standby Unavailable
SHP Office DeltaV 2018-03-21 11:13:34 599 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2018-03-21 11:13:34 645 ALARM PROCESS BOILER CNTRL01 F106 Combustion Air Fan FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2018-03-21 11:13:34 650 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2018-03-21 11:13:34 652 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2018-03-21 11:13:34 654 ALARM INSTRUMENT BOILER CNTRL01 LS107 Boiler HIHI Level PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 11:13:34 1143 ALARM PROCESS BOILER CNTRL01 F105 Boiler Feed Pump FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2018-03-21 11:13:34 2159 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 I/O Input Failure
SHP Office DeltaV 2018-03-21 11:13:34 2161 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 Module Failure Active
SHP Office DeltaV 2018-03-21 11:13:34 2168 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 0 Limit 785
SHP Office DeltaV 2018-03-21 11:13:34 2169 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 750
SHP Office DeltaV 2018-03-21 11:13:34 2171 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 0 Limit 300
SHP Office DeltaV 2018-03-21 11:13:34 2172 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2018-03-21 11:13:34 2174 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2018-03-21 11:13:34 2176 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2018-03-21 11:13:34 2177 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2018-03-21 11:13:34 2655 EVENT PROCESS BOILER CNTRL01 TIC102 Boiler temperature ACTIVE 4-INFO TIC102/PID1 I/O Input Failure
SHP Office DeltaV 2018-03-21 11:13:34 2660 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 0 Limit 80
SHP Office DeltaV 2018-03-21 11:13:34 2662 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature HI_ALM INACT/ACK 11-WARNING HIGH High Alarm Value 0 Limit 60
SHP Office DeltaV 2018-03-21 11:13:34 2663 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400