Event List (669696)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Office DeltaV 2017-12-19 14:55:35 4895 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 14:55:35 5400 EVENT PROCESS BOILER CNTRL01 TIC102 Boiler temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2017-12-19 14:55:35 5899 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2017-12-19 14:55:35 5901 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2017-12-19 14:55:35 5903 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 14:55:34 5418 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2017-12-19 14:55:34 5420 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 20
SHP Office DeltaV 2017-12-19 14:55:34 5421 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 20
SHP Office DeltaV 2017-12-19 14:55:34 5423 ALARM INSTRUMENT BOILER CNTRL01 TIC102 Boiler temperature PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 14:55:34 5893 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 I/O Input Failure
SHP Office DeltaV 2017-12-19 14:55:34 5894 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 Module Failure Active
SHP Office DeltaV 2017-12-19 14:55:34 5896 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 8
SHP Office DeltaV 2017-12-19 14:55:34 5898 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 4
SHP Office DeltaV 2017-12-19 14:55:34 5899 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2017-12-19 14:55:34 5902 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2017-12-19 14:55:34 5904 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2017-12-19 14:55:34 5905 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 0
SHP Office DeltaV 2017-12-19 14:55:34 5907 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 14:55:34 3447 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2017-12-19 14:55:34 3450 ALARM INSTRUMENT BOILER CNTRL01 LS107 Boiler HIHI Level PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 14:55:34 3889 ALARM PROCESS BOILER CNTRL01 F105 Boiler Feed Pump FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2017-12-19 14:55:34 4898 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 I/O Input Failure
SHP Office DeltaV 2017-12-19 14:55:34 4900 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 Module Failure Active
SHP Office DeltaV 2017-12-19 14:55:34 4902 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 0 Limit 785
SHP Office DeltaV 2017-12-19 14:55:34 4904 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 750
SHP Office DeltaV 2017-12-19 14:55:34 4905 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 0 Limit 300
SHP Office DeltaV 2017-12-19 14:55:34 4907 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2017-12-19 14:55:34 4909 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2017-12-19 14:55:34 4910 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2017-12-19 14:55:34 4912 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 14:55:34 5403 EVENT PROCESS BOILER CNTRL01 TIC102 Boiler temperature ACTIVE 4-INFO TIC102/PID1 I/O Input Failure
SHP Office DeltaV 2017-12-19 14:55:34 5413 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 750
SHP Office DeltaV 2017-12-19 14:55:34 5415 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 750
SHP Office DeltaV 2017-12-19 14:55:34 5417 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2017-12-19 14:55:33 2914 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2017-12-19 14:55:33 8070 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:55:33 8230 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:55:33 8318 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:55:33 8393 ALARM PROCESS BOILER CNTRL01 F106 Combustion Air Fan FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2017-12-19 14:55:33 9160 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:55:33 9355 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 14:55:33 9358 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 14:55:33 9360 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE [MULT]IO: Channel Error - AI Card, C01, CH07
SHP Office DeltaV 2017-12-19 14:55:32 7208 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 COMM_ALM INACT/ACK 11-WARNING OK Communications failure
SHP Office DeltaV 2017-12-19 14:55:32 7208 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 14:55:32 7208 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 MAINT_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 14:55:32 7208 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 14:55:31 38 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 14:55:31 273 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2017-12-19 14:55:31 9288 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM INACT/ACK 07-ADVISORY OK IO: Channel Error - AI Card, C01, CH07
SHP Office DeltaV 2017-12-19 14:55:30 3590 ALARM HARDWARE AREA_A PROPLUS PROPLUS FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 14:55:30 3590 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 14:55:30 3590 ALARM HARDWARE AREA_A PROPLUS PROPLUS ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 14:55:30 8915 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:55:29 5010 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:55:27 3640 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:55:27 5670 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 14:55:27 6920 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2017-12-19 14:55:27 8790 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2017-12-19 14:54:01 1290 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:53:50 5210 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:53:47 7440 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:53:46 8080 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 14:53:39 3980 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:53:39 9233 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE [MULT]IO: Channel Error - AI Card, C01, CH07
SHP Office DeltaV 2017-12-19 14:53:38 4082 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:53:38 5325 DOWNLOAD USER AREA_A CNTRL01 IO1/C01 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2017-12-19 14:53:38 6379 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:53:38 6443 DOWNLOAD USER AREA_A CNTRL01 CNTRL01C01CH01 UPDATE Administrator Download Device Alarm
SHP Office DeltaV 2017-12-19 14:53:38 6541 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:53:38 9637 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 14:53:14 1070 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:53:02 1890 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:52:59 6930 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:52:51 1590 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:52:50 1655 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:52:50 3011 DOWNLOAD USER AREA_A CNTRL01 IO1/C01 UPDATE Administrator Partial Download of I/O Card
SHP Office DeltaV 2017-12-19 14:52:50 3990 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:52:50 4051 DOWNLOAD USER AREA_A CNTRL01 CNTRL01C01CH01 UPDATE Administrator Download Device Alarm
SHP Office DeltaV 2017-12-19 14:52:50 4144 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:52:50 7215 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Unit DeltaV 2017-12-19 14:52:47 3600 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 14:51:30 570 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:51:17 5770 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:51:16 6250 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:51:10 9310 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:51:06 5550 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:51:05 6550 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:50:56 6220 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:50:54 6100 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:50:54 8456 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 14:50:53 6944 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:50:53 7002 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:50:51 6191 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:50:51 7309 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 14:50:51 7523 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Unit DeltaV 2017-12-19 14:49:58 8800 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:44:46 8800 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 14:42:12 6270 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 14:42:03 8910 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Unit DeltaV 2017-12-19 14:41:58 4000 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 14:41:51 8320 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:41:49 4770 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:41:40 893 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:41:40 946 DOWNLOAD USER BOILER CNTRL01 PIC101 Steam Pressure UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 14:41:40 1025 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:41:40 4088 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 14:41:40 4955 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 7.59808 Limit 8
SHP Office DeltaV 2017-12-19 14:41:40 4957 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 7.59808 Target 7.54414
SHP Office DeltaV 2017-12-19 14:41:40 7720 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:41:39 7897 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:41:08 8160 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = AUTO
SHP Office DeltaV 2017-12-19 14:41:03 3249 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2017-12-19 14:39:45 4148 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 14:39:45 6881 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 2.14683 Target 2.14683
SHP Office DeltaV 2017-12-19 14:39:44 5171 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure HI_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 14:39:44 6880 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 2.18092 Limit 8
SHP Office DeltaV 2017-12-19 14:39:16 8440 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:39:04 7860 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:39:02 4460 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:38:53 272 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:38:53 320 DOWNLOAD USER BOILER CNTRL01 PIC101 Steam Pressure UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 14:38:53 398 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 14:38:53 3509 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 14:38:53 6863 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 6.67758 Limit 8
SHP Office DeltaV 2017-12-19 14:38:53 7250 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:38:52 7420 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:37:47 5310 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 14:37:40 5822 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM ACT/UNACK 15-CRITICAL HIHI High High Alarm Value 5.1047 Limit 5
SHP Office DeltaV 2017-12-19 14:37:33 2803 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PID1/OUT.CV ADMINISTRATOR NEW VALUE = 15
SHP Office DeltaV 2017-12-19 14:37:26 7659 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2017-12-19 14:37:14 3592 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 14:37:14 5813 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 2.70187 Target 5
SHP Office DeltaV 2017-12-19 14:37:13 5519 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 14:37:13 5811 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 2.63597 Target 5
SHP Office DeltaV 2017-12-19 14:37:10 8090 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:37:10 8537 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PID1/HI_HI_LIM.CV ADMINISTRATOR NEW VALUE = 5
SHP Office DeltaV 2017-12-19 14:37:05 1596 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure HI_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 14:37:05 5805 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 2.21845 Limit 8
SHP Office DeltaV 2017-12-19 14:37:00 450 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 14:36:58 7510 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 14:36:56 3790 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:36:47 88 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 14:36:47 3780 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 14:36:46 3851 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 14:36:46 6804 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 14:36:46 6850 DOWNLOAD USER BOILER CNTRL01 PIC101 Steam Pressure UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 14:36:46 6931 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Unit DeltaV 2017-12-19 14:36:46 4000 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 14:36:33 6640 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 14:33:57 9200 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 14:30:57 1000 CHANGE USER AREA_A PROPLUS LOGOFF OPERATOR
SHP Office DeltaV 2017-12-19 14:30:57 5830 CHANGE USER AREA_A PROPLUS LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 14:30:57 6610 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF OPERATOR
SHP Office DeltaV 2017-12-19 14:30:57 9580 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 14:28:51 1200 CHANGE USER AREA_A PROPLUS REMOTE LOGON OPERATOR
SHP Office DeltaV 2017-12-19 14:28:50 6360 CHANGE USER AREA_A PROPLUS LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 14:28:50 9010 CHANGE USER AREA_A PROPLUS LOGON OPERATOR
SHP Office DeltaV 2017-12-19 14:28:50 9480 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 14:28:45 9200 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:25:57 4400 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:20:45 4400 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:17:56 9600 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:12:44 9590 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:09:56 4790 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:04:44 4790 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 14:01:55 9990 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:56:43 9990 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:53:55 5190 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:48:49 7590 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:46:01 2790 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:40:49 2790 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:39:09 5690 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 13:39:00 2457 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 13:38:59 9719 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 13:38:58 306 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 13:38:58 2456 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 568.98 Limit 300
SHP Office DeltaV 2017-12-19 13:38:57 6856 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 13:38:56 149 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 13:38:56 3560 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 13:38:55 1540 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 13:38:54 4680 CHANGE USER AREA_A PROPLUS PROPLUS MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 13:38:53 5022 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 COMM_ALM INACT/ACK 11-WARNING OK Communications failure
SHP Office DeltaV 2017-12-19 13:38:53 5028 CHANGE USER AREA_A PROPLUS CNTRL01C01CH01 COMM_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 13:38:52 68 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure PVBAD_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 13:38:52 3947 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 13:38:47 3390 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 13:38:45 5140 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:38:36 2445 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2017-12-19 13:38:36 2449 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 569.004 Limit 300
SHP Office DeltaV 2017-12-19 13:38:35 344 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 13:38:35 399 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 13:38:35 478 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 13:38:35 3666 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 13:38:35 7480 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 13:38:34 7613 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 13:38:34 9289 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Unit DeltaV 2017-12-19 13:38:00 7980 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:36:48 4670 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 13:36:36 9070 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 13:36:35 1570 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 13:36:26 4877 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2017-12-19 13:36:26 4880 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 284.466 Limit 300
SHP Office DeltaV 2017-12-19 13:36:25 351 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 13:36:25 411 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 13:36:25 551 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 13:36:25 3603 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 13:36:25 4885 CHANGE USER BOILER CNTRL01 LIC103 Hotwell Level PID1/SP_HI_LIM.CV FUNCTION_BLOCK NEW VALUE = 500.000000
SHP Office DeltaV 2017-12-19 13:36:25 7170 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 13:36:24 7329 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 13:36:24 9345 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2017-12-19 13:36:05 4650 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 13:35:53 7380 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 13:35:51 700 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 13:35:43 2361 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1/PV_SCALE Inputs Transfer Failure
SHP Office DeltaV 2017-12-19 13:35:42 182 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 13:35:42 3650 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 13:35:41 3809 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 13:35:41 5792 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2017-12-19 13:35:41 6830 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 13:35:41 6900 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 13:35:41 7017 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Unit DeltaV 2017-12-19 13:32:48 7990 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:31:03 7470 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:30:58 2250 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 13:30:00 3190 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:28:41 6038 CHANGE USER BOILER PROPLUS DEMO1 Control Module SWITCH.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 13:26:53 5584 CHANGE USER BOILER PROPLUS DEMO1 Control Module IN1.CV ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 13:25:43 5340 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:25:37 9490 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 13:24:48 3180 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:24:00 6990 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:23:55 7690 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 13:21:59 8380 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:18:54 640 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:18:50 8040 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:17:43 8340 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:17:08 1090 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:16:55 3020 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 13:16:47 8390 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:13:59 3580 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:11:32 8180 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:10:47 1100 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Office DeltaV 2017-12-19 13:10:04 9430 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 13:09:47 3444 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM INACT/ACK 07-ADVISORY OK Configuration Change
SHP Office DeltaV 2017-12-19 13:09:47 3444 EVENT DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALERTS 4-INFO Condition Cleared Configuration Change
SHP Office DeltaV 2017-12-19 13:09:46 6373 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE Configuration Change
SHP Office DeltaV 2017-12-19 13:09:46 6373 EVENT DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALERTS 4-INFO Condition Set Configuration Change
SHP Office DeltaV 2017-12-19 13:09:45 2221 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM INACT/ACK 07-ADVISORY OK Cold Start
SHP Office DeltaV 2017-12-19 13:09:45 2221 EVENT DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALERTS 4-INFO Condition Cleared Cold Start
SHP Office DeltaV 2017-12-19 13:09:44 5559 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 COMM_ALM INACT/UNACK 11-WARNING COMM Communications failure
SHP Office DeltaV 2017-12-19 13:09:44 5559 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE Cold Start
SHP Office DeltaV 2017-12-19 13:09:44 5559 EVENT DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALERTS 4-INFO Condition Set Cold Start
SHP Office DeltaV 2017-12-19 13:09:43 5928 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM INACT/ACK 07-ADVISORY OK IO: Channel Error - AI Card, C01, CH01
SHP Office DeltaV 2017-12-19 13:09:34 9030 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 13:09:25 5920 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE IO: Channel Error - AI Card, C01, CH01
SHP Office DeltaV 2017-12-19 13:09:24 454 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 COMM_ALM ACT/UNACK 11-WARNING COMM Communications failure
SHP Unit DeltaV 2017-12-19 13:08:47 3580 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 13:07:31 6690 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Unit DeltaV 2017-12-19 13:05:58 8780 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 13:00:46 8780 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:58:15 290 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:58:00 5840 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2017-12-19 12:57:59 8970 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2017-12-19 12:57:58 7120 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Unit DeltaV 2017-12-19 12:57:58 3980 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:57:56 8870 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:57:53 8290 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:57:42 7840 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:56:51 2490 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:56:38 7690 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:56:36 8500 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:56:27 641 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 12:56:27 4280 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:56:26 4358 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 12:56:26 6306 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2017-12-19 12:56:26 7305 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 12:56:26 7359 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 12:56:26 7438 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Unit DeltaV 2017-12-19 12:52:46 3980 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:49:57 9180 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:44:54 2226 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 6.5 Limit 400
SHP Office DeltaV 2017-12-19 12:44:53 2226 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 6.58976 Target 5
SHP Office DeltaV 2017-12-19 12:44:53 4764 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure LO_ALM.ENAB ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 12:44:52 2225 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 6.67758 Target 5
SHP Office DeltaV 2017-12-19 12:44:52 3805 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 12:44:51 2224 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 6.76336 Limit 400
SHP Office DeltaV 2017-12-19 12:44:51 4678 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_LO_ALM.ENAB ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 12:44:50 2224 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 6.84698 Target 5
SHP Office DeltaV 2017-12-19 12:44:50 6847 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure LO_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 12:44:49 2224 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 6.92836 Target 5
SHP Office DeltaV 2017-12-19 12:44:49 5340 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_LO_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 12:44:48 8621 CHANGE USER BOILER PROPLUS PIC101 Steam Pressure DV_HI_ALM.ENAB ADMINISTRATOR NEW VALUE = 1
SHP Unit DeltaV 2017-12-19 12:44:45 9180 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:43:09 4535 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/OUT.CV ADMINISTRATOR NEW VALUE = 17.82
SHP Office DeltaV 2017-12-19 12:43:05 9408 CHANGE USER BOILER PROPLUS TIC102 Boiler temperature PID1/MODE.TARGET ADMINISTRATOR NEW VALUE = MAN
SHP Office DeltaV 2017-12-19 12:42:56 2465 CHANGE USER BOILER PROPLUS F106 Combustion Air Fan DC1/SP_D.CV ADMINISTRATOR NEW VALUE = START
SHP Office DeltaV 2017-12-19 12:42:52 1199 CHANGE USER BOILER PROPLUS F106 Combustion Air Fan DC1/SP_D.CV ADMINISTRATOR NEW VALUE = STOP
SHP Unit DeltaV 2017-12-19 12:41:57 4380 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:36:45 4380 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:33:56 9580 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:31:12 4886 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2017-12-19 12:31:10 9885 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Unit DeltaV 2017-12-19 12:28:44 9570 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:26:23 1290 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:26:18 1840 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:26:08 7460 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:26:06 9453 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 12:26:05 8178 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 12:26:05 8263 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 12:26:05 8440 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:26:03 4570 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 12:26:03 8288 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 12:26:03 9480 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 12:26:03 9690 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2017-12-19 12:26:02 220 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2017-12-19 12:26:01 5850 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 12:26:01 7100 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 12:26:01 8350 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Unit DeltaV 2017-12-19 12:25:56 4770 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:24:52 5980 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:24:38 2310 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:24:36 5770 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 12:24:25 2360 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 12:24:24 2526 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 12:24:24 4750 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 12:24:24 4807 DOWNLOAD USER BOILER CNTRL01 DEMO1 Control Module UPDATE Administrator Partial Download of Module
SHP Office DeltaV 2017-12-19 12:24:24 4894 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 12:24:24 7503 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 12:22:16 7370 CHANGE USER AREA_A PROPLUS REMOTE LOGOFF ADMINISTRATOR
SHP Office DeltaV 2017-12-19 12:21:53 1030 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 12:20:44 4770 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:17:55 9970 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:12:43 9970 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:09:55 5170 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 12:09:17 5660 CHANGE USER AREA_A PROPLUS REMOTE LOGON ADMINISTRATOR
SHP Unit DeltaV 2017-12-19 12:04:43 5170 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 12:01:55 370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:56:43 370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:53:54 5570 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:51:32 4750 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 11:51:27 7790 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 11:51:18 1070 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 11:51:16 1890 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 11:51:16 3148 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 11:51:15 2107 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 11:51:15 2190 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 11:51:13 1471 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 11:51:13 2629 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 11:51:13 2836 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Office DeltaV 2017-12-19 11:50:58 1470 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 11:50:56 2440 DOWNLOAD USER AREA_A PROPLUS PROPLUS UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 11:50:56 3690 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 11:50:56 4930 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/MODT UPDATE Administrator Module names and node assignments
SHP Office DeltaV 2017-12-19 11:50:56 6810 DOWNLOAD USER AREA_A PROPLUS SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Unit DeltaV 2017-12-19 11:48:42 5570 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:45:54 770 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:40:42 770 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:37:53 5970 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:32:41 5970 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:29:53 1170 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:29:14 5620 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:29:03 1900 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 11:28:55 2725 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Standby Unavailable
SHP Office DeltaV 2017-12-19 11:28:52 3480 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 11:28:49 8050 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 11:28:45 2712 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Standby Unavailable
SHP Office DeltaV 2017-12-19 11:28:44 3370 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 completed successfully
SHP Office DeltaV 2017-12-19 11:28:44 4986 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 11:28:44 5170 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: NO CONFIGURATION
SHP Office DeltaV 2017-12-19 11:28:41 170 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 11:28:40 8806 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2017-12-19 11:28:40 8807 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2017-12-19 11:28:40 8809 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 568.98 Limit 300
SHP Office DeltaV 2017-12-19 11:28:40 8811 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 11:28:40 9309 EVENT PROCESS BOILER CNTRL01 TIC102 Boiler temperature ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2017-12-19 11:28:40 9803 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2017-12-19 11:28:40 9804 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO Error Cleared Module Failure Active
SHP Office DeltaV 2017-12-19 11:28:40 9805 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 11:28:39 2197 DOWNLOAD USER BOILER CNTRL01 LIC103 Hotwell Level UPDATE Administrator Attribute Override Failure: PID1/OUT_HI_LIM TO 1000
SHP Office DeltaV 2017-12-19 11:28:39 2702 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 FAILED_ALM INACT/ACK 11-WARNING OK Node: Node not configured
SHP Office DeltaV 2017-12-19 11:28:39 2705 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 11:28:39 2707 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 11:28:39 7310 ALARM PROCESS BOILER CNTRL01 LS107 Boiler HIHI Level DISC_ALM INACT/ACK 11-WARNING DI_ALM Normal
SHP Office DeltaV 2017-12-19 11:28:39 7312 ALARM INSTRUMENT BOILER CNTRL01 LS107 Boiler HIHI Level PV_BAD INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 11:28:39 7332 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator End of download. - 0
SHP Office DeltaV 2017-12-19 11:28:39 7399 ALARM PROCESS BOILER CNTRL01 F106 Combustion Air Fan FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2017-12-19 11:28:39 7500 EVENT SYSTEM AREA_A PROPLUS COLD_RESTART DOWNLOAD 4-INFO Cold restart on CNTRL01 started
SHP Office DeltaV 2017-12-19 11:28:39 7801 ALARM PROCESS BOILER CNTRL01 F105 Boiler Feed Pump FAIL_ALM INACT/ACK 11-WARNING FAILED Clear
SHP Office DeltaV 2017-12-19 11:28:39 8823 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 I/O Input Failure
SHP Office DeltaV 2017-12-19 11:28:39 8824 EVENT PROCESS BOILER CNTRL01 LIC103 Hotwell Level ACTIVE 4-INFO LIC103/PID1 Module Failure Active
SHP Office DeltaV 2017-12-19 11:28:39 8826 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_HI_ALM INACT/ACK 15-CRITICAL HIHI High High Alarm Value 0 Limit 785
SHP Office DeltaV 2017-12-19 11:28:39 8828 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 750
SHP Office DeltaV 2017-12-19 11:28:39 8829 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM ACT/UNACK 11-WARNING LOW Low Alarm Value 0 Limit 300
SHP Office DeltaV 2017-12-19 11:28:39 8831 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2017-12-19 11:28:39 8833 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_HI_ALM INACT/ACK 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2017-12-19 11:28:39 8834 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 483
SHP Office DeltaV 2017-12-19 11:28:39 8835 ALARM INSTRUMENT BOILER CNTRL01 LIC103 Hotwell Level PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 11:28:39 9313 EVENT PROCESS BOILER CNTRL01 TIC102 Boiler temperature ACTIVE 4-INFO TIC102/PID1 I/O Input Failure
SHP Office DeltaV 2017-12-19 11:28:39 9318 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 750
SHP Office DeltaV 2017-12-19 11:28:39 9320 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 750
SHP Office DeltaV 2017-12-19 11:28:39 9322 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2017-12-19 11:28:39 9323 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2017-12-19 11:28:39 9325 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 20
SHP Office DeltaV 2017-12-19 11:28:39 9326 ALARM PROCESS BOILER CNTRL01 TIC102 Boiler temperature DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 20
SHP Office DeltaV 2017-12-19 11:28:39 9328 ALARM INSTRUMENT BOILER CNTRL01 TIC102 Boiler temperature PVBAD_ALM INACT/ACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 11:28:39 9806 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 I/O Input Failure
SHP Office DeltaV 2017-12-19 11:28:39 9808 EVENT PROCESS BOILER CNTRL01 PIC101 Steam Pressure ACTIVE 4-INFO PIC101/PID1 Module Failure Active
SHP Office DeltaV 2017-12-19 11:28:39 9810 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_HI_ALM DISABLED 15-CRITICAL HIHI High High Alarm Value 0 Limit 8
SHP Office DeltaV 2017-12-19 11:28:39 9811 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure HI_ALM DISABLED 11-WARNING HIGH High Alarm Value 0 Limit 4
SHP Office DeltaV 2017-12-19 11:28:39 9813 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_ALM DISABLED 11-WARNING LOW Low Alarm Value 0 Limit 400
SHP Office DeltaV 2017-12-19 11:28:39 9816 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure LO_LO_ALM DISABLED 15-CRITICAL LOLO Low Low Alarm Value 0 Limit 250
SHP Office DeltaV 2017-12-19 11:28:39 9818 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_HI_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 5
SHP Office DeltaV 2017-12-19 11:28:39 9819 ALARM PROCESS BOILER CNTRL01 PIC101 Steam Pressure DV_LO_ALM DISABLED 07-ADVISORY DEV Deviation Alarm Actual 0 Target 5
SHP Office DeltaV 2017-12-19 11:28:39 9821 ALARM INSTRUMENT BOILER CNTRL01 PIC101 Steam Pressure PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2017-12-19 11:28:38 7171 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 COMM_ALM INACT/ACK 11-WARNING OK Communications failure
SHP Office DeltaV 2017-12-19 11:28:38 7171 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 FAILED_ALM INACT/ACK 11-WARNING OK <None>
SHP Office DeltaV 2017-12-19 11:28:38 7171 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 MAINT_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 11:28:38 7171 ALARM DEVICE AREA_A CNTRL01 CNTRL01C01CH01 ADVISE_ALM INACT/ACK 07-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 11:28:37 111 DOWNLOAD USER AREA_A CNTRL01 CNTRL01 UPDATE Administrator Start of Download - 0
SHP Office DeltaV 2017-12-19 11:28:37 1499 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/DT UPDATE Administrator System node names, addresses
SHP Office DeltaV 2017-12-19 11:28:37 1706 DOWNLOAD USER AREA_A CNTRL01 SYSTEM_DATA/APT UPDATE Administrator System-wide setup data
SHP Unit DeltaV 2017-12-19 11:24:41 1170 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:24:25 2538 EVENT SYSTEM AREA_A CNTRL01 CONT ACTIVE 4-INFO Completed controller reset initialization.
SHP Office DeltaV 2017-12-19 11:23:59 180 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:23:43 9950 STATUS SYSTEM AREA_A PROPLUS CNTRL01 NO CONFIGURATION 4-INFO Previous node status was: NOT COMMUNICATING
SHP Office DeltaV 2017-12-19 11:23:41 3600 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2017-12-19 11:23:26 1692 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 FAILED_ALM ACT/UNACK 12-CRITICAL FAILED Node: Node not configured
SHP Office DeltaV 2017-12-19 11:23:26 1695 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM DISABLED 04-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 11:23:26 1697 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM DISABLED 04-ADVISORY OK <None>
SHP Office DeltaV 2017-12-19 11:23:08 4130 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Unit DeltaV 2017-12-19 11:21:52 6370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:19:58 1700 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:19:41 3610 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Unit DeltaV 2017-12-19 11:16:40 6370 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 11:13:52 1570 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:12:39 6589 EVENT SYSTEM AREA_A CNTRL01 CONT ACTIVE 4-INFO Completed controller reset initialization.
SHP Office DeltaV 2017-12-19 11:12:27 3570 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:12:12 3340 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:12:11 6559 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2017-12-19 11:12:08 8303 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Available
SHP Office DeltaV 2017-12-19 11:11:57 3110 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:11:57 3110 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:11:55 3610 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2017-12-19 11:11:41 3630 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2017-12-19 11:11:41 6523 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2017-12-19 11:11:40 1223 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Switchover Occurred
SHP Office DeltaV 2017-12-19 11:11:40 1224 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Unavailable
SHP Office DeltaV 2017-12-19 11:09:01 790 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:08:55 3230 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM INACT/ACK 07-ADVISORY OK Redundancy: Not Communicating - Primary Network
SHP Unit DeltaV 2017-12-19 11:08:40 1560 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:08:35 3206 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2017-12-19 11:08:35 3209 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 ADVISE_ALM ACT/ACK 07-ADVISORY ADVISE Redundancy: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:07:43 3180 EVENT SYSTEM AREA_A CNTRL01 CONT ACTIVE 4-INFO Completed controller reset initialization.
SHP Office DeltaV 2017-12-19 11:07:08 5995 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Available
SHP Office DeltaV 2017-12-19 11:06:49 3886 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2017-12-19 11:06:49 7440 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2017-12-19 11:06:45 3193 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2017-12-19 11:06:43 6659 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Switchover Occurred
SHP Office DeltaV 2017-12-19 11:06:43 6664 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-83-3C Standby is now Unavailable
SHP Office DeltaV 2017-12-19 11:06:40 5680 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Device Connection Failure - CNTRL01
SHP Office DeltaV 2017-12-19 11:06:39 680 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2017-12-19 11:06:38 280 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:06:32 6483 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:06:22 9950 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2017-12-19 11:06:21 1657 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Office DeltaV 2017-12-19 11:06:03 6459 EVENT SYSTEM AREA_A CNTRL01 CONT ACTIVE 4-INFO Completed controller reset initialization.
SHP Office DeltaV 2017-12-19 11:05:51 7170 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Unit DeltaV 2017-12-19 11:05:51 6760 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 11:05:44 6456 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2017-12-19 11:05:42 888 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Available
SHP Office DeltaV 2017-12-19 11:05:36 6940 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:05:25 3680 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2017-12-19 11:05:21 6610 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:05:21 6610 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:05:14 6439 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Office DeltaV 2017-12-19 11:05:11 3530 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT [MULT]ACN Communications: Not Communicating - Secondary Network
SHP Office DeltaV 2017-12-19 11:05:04 5151 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Switchover Occurred
SHP Office DeltaV 2017-12-19 11:05:04 5153 EVENT SYSTEM AREA_A CNTRL01 REDU 00-80-74-01-ED-22 Standby is now Unavailable
SHP Office DeltaV 2017-12-19 11:04:06 9250 STATUS SYSTEM AREA_A PROPLUS PROPLUS OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:04:06 9250 STATUS SYSTEM AREA_A PROPLUS CNTRL01 OK 4-INFO Previous node status was: BAD INTEGRITY
SHP Office DeltaV 2017-12-19 11:04:04 2641 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM INACT/ACK 11-WARNING OK ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:04:04 4328 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Primary ACN - PROPLUS
SHP Office DeltaV 2017-12-19 11:03:55 3660 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM INACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:03:54 6950 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Primary ACN - CNTRL01
SHP Office DeltaV 2017-12-19 11:03:21 8410 STATUS SYSTEM AREA_A PROPLUS PROPLUS BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:03:18 274 CHANGE USER AREA_A PROPLUS CNTRL01 ALARMS.MACK ADMINISTRATOR NEW VALUE = 1
SHP Office DeltaV 2017-12-19 11:03:18 314 CHANGE USER AREA_A PROPLUS CNTRL01 MAINT_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 11:03:18 2616 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/ACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:03:11 3620 ALARM HARDWARE AREA_A PROPLUS PROPLUS MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:03:06 8020 STATUS SYSTEM AREA_A PROPLUS CNTRL01 BAD INTEGRITY 4-INFO Previous node status was: OK
SHP Office DeltaV 2017-12-19 11:03:04 2608 ALARM HARDWARE AREA_A CNTRL01 CNTRL01 MAINT_ALM ACT/UNACK 11-WARNING MAINT ACN Communications: Not Communicating - Primary Network
SHP Office DeltaV 2017-12-19 11:03:01 6370 EVENT SYSTEM AREA_A PROPLUS ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - CNTRL01
SHP Office DeltaV 2017-12-19 11:02:59 7794 EVENT SYSTEM AREA_A CNTRL01 ACN COMM ACTIVE 4-INFO Switched to Secondary ACN - PROPLUS
SHP Unit DeltaV 2017-12-19 11:00:39 6760 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 10:57:51 1960 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Unit DeltaV 2017-12-19 10:52:39 1960 EVENT SYSTEM AREA_A AS01 ACN COMM ACTIVE 4-INFO Device Connection Failure - WS01
SHP Office DeltaV 2017-12-19 10:51:32 4340 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/ACK 11-WARNING LOW Low Alarm Value 568.933 Limit 300
SHP Office DeltaV 2017-12-19 10:51:31 7702 CHANGE USER BOILER PROPLUS LIC103 Hotwell Level LO_ALM.NALM ADMINISTRATOR NEW VALUE = 0
SHP Office DeltaV 2017-12-19 10:51:06 4327 ALARM PROCESS BOILER CNTRL01 LIC103 Hotwell Level LO_ALM INACT/UNACK 11-WARNING LOW Low Alarm Value 396.315 Limit 300